Reports Reference

This section provides full documentation for every report currently available through the Resolute platform. Each report is described in its own subsection and provides the following information:

  • Report name
  • Current report status
    • ‘Beta’ status is considered experimental in that the contents and the algorithms are still being vetted out
    • ‘GA’ (General Availability) status is considered stable and will not be subjected to the same frequency or scope of changes
  • Report description
  • Equipment type associated with the report
  • Any additional equipment constraints in the form of equipment tags that must be present before a given piece of equipment appears in the report
  • Any special tuple constraints stipulating the presence or absence of multiple input points
  • The set of standard input points, including:
    • What point template must be applied to the point?
    • Expected point position in the building hierarchy relative to the piece of equipment to which the rule will be applied
    • Definition as a mandatory or optional input point
    • Definition as a scalar or vector input point
  • The set of rule input points, including:
    • Rule name
    • Definition as a mandatory or optional input point

Air Terminal Unit Operations

Summary

This report scores VAV boxes based on their ability to maintain zone temperature and airflow setpoints, along with potential root causes.

Status Equipment Type Equipment Tag or Tuple Constraints
GA vav For a given VAV to be included in the report, it must include either an ‘EffCoolSp’ input point, an ‘EffHeatSp’ input point, or a ZoneTempDev point. If none of these points exist, then the VAV will not be included in the report.

Standard Input Points

Name Point Template Positional Requirements Optionality Multiplicity
ZoneTemp ZoneTemp This point must be a direct child of the equipment. Mandatory Scalar
EffCoolSp EffCoolSp This point must be a direct child of the equipment. Optional (but see the tuple constraint for this report) Scalar
EffHeatSp EffHeatSp This point must be a direct child of the equipment. Optional (but see the tuple constraint for this report) Scalar
ZoneTempDev ZoneTempDev This point must be a direct child of the equipment. Optional (but see the tuple constraint for this report) Scalar
DaFlow DaFlow This point must be a direct child of the equipment. Optional Scalar
DaFlowSp DaFlowSp This point must be a direct child of the equipment. Optional Scalar
DaTemp DaTemp This point must be a direct child of the equipment. Optional Scalar
DmprCmd DmprCmd This point must be a direct child of the equipment. Optional Scalar
RhtCmd RhtCmd This point must be a direct child of the equipment. Optional Scalar
ZoneTempSp ZoneTempSp This point must be a direct child of the equipment.  Optional Scalar
DaTemp DaTemp This point must be a direct child of the equipment Optional Scalar
ColdDeckDmprCmd ColdDeckDmprCmd This point must be a direct child of the equipment Optional Scalar
HotDeckDmprCmd HotDeckDmprCmd This point must be a direct child of the equipment Optional Scalar
DaFanSts DaFanSts This point must be a direct child of the parent AHU of the equipment. Optional Scalar

Rule Input Points

Name Rule Optionality
Rule 3.2.33.1 3.2.33.1 - Zone Temperature is Less Than Setpoint Mandatory
Rule 3.2.34.1 3.2.34.1 - Zone Temperature is Greater Than Setpoint Mandatory
Rule 3.1.16.1 Parent Equipment: 3.1.16.1 - Discharge Fan Static Pressure is Greater Than Setpoint Optional
Rule 3.1.17.1 Parent Equipment: 3.1.17.1 - Discharge Fan Static Pressure is Less Than Setpoint Optional
Rule 3.1.20.1 Parent Equipment: 3.1.20.1 - Fan Status Off When Commanded On Optional
Rule 3.1.21.1 Parent Equipment: 3.1.21.1 - Fan Status On When Commanded Off Optional
Rule 3.1.33.1 Parent Equipment: 3.1.33.1 - Discharge Air Temperature is Greater Than Setpoint Optional
Rule 3.1.34.1 Parent Equipment: 3.1.34.1 - Discharge Air Temperature is Less Than Setpoint Optional
Rule 3.2.5.1 3.2.5.1 - Unexpected Increase in VAV Discharge Temperature Optional
Rule 3.2.6.1  3.2.6.1 - Cooling Mode With No Flow Optional 
Rule 3.2.7.1 3.2.7.1 - Cooling Mode with Low Flow Optional
Rule 3.2.9.1 3.2.9.1 - VAV Zone Temperature Sensor Failure Optional
Rule 3.2.9.2 3.2.9.1 - VAV Discharge Air Temperature Sensor Failure Optional
Rule 3.2.16.1 3.2.16.1 - Occupied Zone Temperature Heating Setpoint Above High Limit Optional
Rule 3.2.17.1 3.2.17.1 - Occupied Zone Temperature Cooling Setpoint Below Low Limit  Optional
Rule 3.2.18.1 3.2.18.1 - VAV Discharge Airflow Sensor Failure Optional
Rule 3.2.23.1 3.2.23.1 - Leaking Damper Optional
Rule 3.2.24.1 3.2.24.1 - Low Discharge Air Temperature Optional
Rule 3.2.25.1 3.2.25.1 - Leaking Reheat Valve Optional
Rule 3.2.31.1 3.2.31.1 - Multi Zone Unexpected Temperature Decrease When Cold Deck Damper is Closed Optional
Rule 3.2.32.1 3.2.32.1 - Multi Zone Unexpected Temperature Increase When Hot Deck Damper is Closed Optional
Rule 3.2.37.1 3.2.37.1 - Zone Temperature Heating Setpoint is Higher Than Cooling Setpoint Optional
Rule 3.2.38.1 3.2.38.1 - Minimum Airflow Setpoint is Greater Than the Maximum Airflow Setpoint Optional

VAV Controller Performance Report

Summary

This report evaluates Variable Air Volume Box (VAV) airflow damper and reheat valve commands based on total actuator movement and oscillations over time.

Status Status Equipment Tag or Tuple Constraints
GA vav For a given VAV to be included   in the report, it must include either an ‘DmprCmd’ input point or an ‘RhtCmd’   input point. If neither of these   points exist, then the VAV will not be included in the report.

Standard Input Points

Name Point Template Data Type Requirement Positional Requirement Optionality Multiplicity
DmprCmd DmprCmd Numeric This point must be a direct child of the equipment. Optional (but see the tuple constraint for this report) Scalar
RhtCmd RhtCmd Numeric This point must be a direct child of the equipment. Optional (but see the tuple constraint for this report) Scalar
DaFanSts DaFanSts -- This point must be a direct child of the parent AHU of the equipment. Optional Scalar

Rule Input Points

None

AHU Operations Report

Summary

This report scores air handling units based on the equipment’s ability to maintain discharge temperature and pressure setpoints, along with potential root causes.

Status Equipment Type Tuple and Equipment Tag Constraints
GA ahu

Tuple

For a given AHU to be included in the report, it must contain the following:


DaTemp and DaTempSp

or

ColdDeckTemp, HotDeckTemp, ColdDeckTempSp, and HotDeckTempSp

and

Rule 3.1.33.1 and Rule 3.1.33.2

or 

Rule 3.1.33.2, Rule 3.1.33.3, Rule 3.1.34.2, and Rule 3.1.34.3


Equipment Tag

If the given AHU has a heating tag, but does not have a cooling tag, or if the AHU has the DirectZone tag, it will not be included in the report. 

Standard Input Points

Name Point Template Positional Requirements Optionality Multiplicity
DaFanSts DaFanSts This point must be a direct child of the equipment. Mandatory Scalar
DaTemp DaTemp This point must be a direct child of the equipment. Optional Scalar
DaTempSp DaTempSp This point must be a direct child of the equipment. Optional Scalar
DaPress DaPress This point must be a direct child of the equipment. Optional Scalar
DaPressSp DaPressSp This point must be a direct child of the equipment. Optional Scalar
ClgCmd ClgCmd This point must be a direct child of the equipment. Optional Scalar
OaDmprCmd OsDmprCmd This point must be a direct child of the equipment. Optional Scalar
DaFanSp DaFanSp This point must be a direct child of the equipment. Optional Scalar
HtgCmd HtgCmd This point must be a direct child of the equipment. Optional Scalar
ColdDeckTemp ColdDeckTemp This point must be a direct child of the equipment. Optional Scalar
ColdDeckTempSp ColdDeckTempSp This point must be a direct child of the equipment. Optional Scalar
HotDeckTemp HotDeckTemp This point must be a direct child of the equipment. Optional Scalar
HotDeckTempSp HotDeckTempSp This point must be a direct child of the equipment. Optional Scalar

Rule Input Points

Name Rule Optionality
Rule 3.1.1.1 3.1.1.1 - AHU Simultaneous Heating and Cooling Optional
Rule 3.1.4.1 3.1.4.1 - Outside Air Damper Position is Greater Than Minimum Setpoint During Heating Mode Optional
Rule 3.1.4.2 3.1.4.2 - Outside Airflow is Greater Than Minimum Setpoint During Heating Mode Optional
Rule 3.1.4.3 3.1.4.3 - Outside Air Damper Position is Greater Than Minimum Setpoint During Mechanical Cooling Mode Optional
Rule 3.1.4.4 3.1.4.4 - Outside Airflow is Greater Than Minimum Setpoint During Mechanical Cooling Mode Optional
Rule 3.1.6.1  3.1.6.1 - Percent Outside Air Calculated is Greater Than Outside Air Damper Command Optional
Rule 3.1.6.2  3.1.6.2 - Outside Air Fraction is Too High Compared to Minimum Outside Airflow Setpoint Optional
 Rule 3.1.9.1 3.1.9.1 - Discharge Air Temperature Sensor Failure Optional
Rule 3.1.9.2 3.1.9.2 - Mixed Air Temperature Sensor Failure Optional
Rule 3.1.9.3 3.1.9.3 - Return Air Temperature Sensor Failure Optional
Rule 3.1.9.4 3.1.9.4 - Outside Air Temperature Sensor Failure Optional
Rule 3.1.10.1 3.1.10.1 - Discharge Air Pressure Sensor Failure Optional
Rule 3.1.14.1 3.1.14.1 - Discharge Air Fan VFD Invariant Optional
Rule 3.1.14.2 3.1.14.2 - Discharge Air Fan VFD Invariant  Optional
Rule 3.1.16.1 3.1.16.1 - Discharge Fan Static Pressure is Greater Than Setpoint Optional
Rule 3.1.17.1 3.1.17.1 - Discharge Fan Static Pressure is Less Than Setpoint Optional
Rule 3.1.20.1 3.1.20.1 - Fan Status Off When Commanded On Optional
Rule 3.1.21.1 3.1.21.1 - Fan Status On When Commanded Off Optional
Rule 3.1.33.1  3.1.33.1 - Discharge Air Temperature is Greater Than Setpoint Optional
Rule 3.1.33.2  3.1.33.2 - Hot Deck Air Temperature is Greater Than Setpoint Optional
Rule 3.1.33.3 3.1.33.3 - Cold Deck Air Temperature is Greater Than Setpoint Optional
Rule 3.1.34.1 3.1.34.1 - Discharge Air Temperature is Less Than Setpoint Optional
Rule 3.1.34.2 3.1.34.2 - Hot Deck Air Temperature is Less Than Setpoint Optional
Rule 3.1.34.3 3.1.34.3 - Cold Deck Air Temperature is Less Than Setpoint Optional
Rule 3.1.35.1 3.1.35.1 Unexpected Temperature Decrease Across Cooling Coil Optional
Rule 3.1.36.1 3.1.36.1 - Unexpected Temperature Increase Across Heating Coil Optional
Rule 3.1.37.1 3.1.37.1 - Low Temperature Differential Across Cooling Coil Optional
Rule 3.1.38.1  3.1.38.1 - Low Temperature Differential Across Heating Coil Optional
Rule 3.1.50.1 3.1.50.1 - Hot Deck Temperature Not Rising in Temperature with Heating Command On Optional
Rule 3.1.51.1 3.1.51.1 - Cold Deck Temperature Not Dropping in Temperature with Cooling Command On Optional

AHU Controller Performance Report

Summary

This report evaluates air handling unit (AHU) cooling valve, heating valve, and outside air damper commands based on total actuator movement and oscillations over time.

Status Equipment Type Equipment Tag or Tuple Constraints
GA ahu For a given AHU to be included in the report, it must include either a ‘ClgCmd’ input point, or a ‘HtgCmd’ input point, or an ‘OaDmprCmd’ point. If none of these points exist, then the AHU will not be included in the report.

Standard Input Points

Name Point Template Data Type Requirement Positional Requirement Optionality Multiplicity
ClgCmd ClgCmd Numeric This point must be a direct child of the equipment. Optional (but see the tuple constraint for this report). Scalar

HtgCmd


HtgCmd Numeric This point must be a direct child of the equipment. Optional (but see the tuple constraint for this report). Scalar

OaDmprCmd


OaDmprCmd -- This point must be a direct child of the equipment. Optional (but see the tuple constraint for this report). Scalar
DaFanSts DaFanSts -- This point must be a direct child of the parent AHU of the equipment. Optional Scalar

Rule Input Points

None.

AHU Schedule Report

Summary 

The purpose of the AHU schedule report is to determine when AHUs are not running according to a predefined building schedule set by the user in RBI Synergy.

Status Equipment Type Equipment Tag or Tuple Constraints
GA ahu None

Standard Input Points

Name Point Template Positional Requirements Optionality Multiplicity
ScheduledOccSt ScheduledOccSt This point must be a direct child of the parent AHU of the equipment. Mandatory Scalar
DaFanSts DaFanSts This point must be a direct child of the parent AHU of the equipment. Mandatory Scalar

AHU Economizer Report

Summary

This report evaluates Air Handling Unit (AHU) economizer operation (free cooling) and outside airflow and provides a score based on the effectiveness of both. Fault conditions contributing to the score are: 

  1. Weather conditions permit free cooling, but is not being fully utilized.
  2. Excessive outside air is entering the building resulting in additional heating or cooling. A relative cost is calculated to project the impact of these conditions.
Status Equipment Type Equipment Tag or Tuple Constraints
GA ahu

Tuple:

For a given AHU to be included in the report, it must include all of the following:


1. Either both ‘OaHumidity’ and “OaTemp” input points or both ‘OffPremWeatherStation’ Humidity and ‘OffPremWeatherStation’ Temp input points. 

2. Either both “DaFlow” and “OaFlow” input points, or both “MaTemp” and “RaTemp” input points, or “OaDmprCmd” input point.

3. Either both ‘OaFlowMinSp’ and ‘DaFlow’ input points, or ‘OaDmprMinPosSp’ input point.

4. At least one of either “ColdDedkTempSp” input point, or “ColdDeckTemp” input point, or “DaTempSp” input point, or “DaTemp” input point.


If any one of the above are not met, then the AHU will not be included in the report.


Equipment Tag:

If the given AHU has the 100% Makeup Unit tag, the AHU will not be included in the report.

Standard Input Points

Name Point Template Positional Requirements Optionality Multiplicity
DaFanSts DaFanSts This point must be a direct child of the equipment. Mandatory Scalar
ClgCmd ClgCmd This point must be a direct child of the equipment. Mandatory Scalar
ColdDeckTemp ColdDeckTemp This point must be a direct child of the equipment. Optional (but see the tuple constraint for this report). Scalar
ColdDeckTempSp ColdDeckTempSp This point must be a direct child of the equipment. Optional (but see the tuple constraint for this report). Scalar
DaFlow DaFlow This point must be a direct child of the equipment. Optional (but see the tuple constraint for this report). Scalar
DaTemp DaTemp This point must be a direct child of the equipment. Optional (but see the tuple constraint for this report). Scalar
DaTempSp DaTempSp This point must be a direct child of the equipment. Optional (but see the tuple constraint for this report). Scalar
MaTemp MaTemp This point must be a direct child of the equipment. Optional (but see the tuple constraint for this report). Scalar
OaDmprCmd OaDmprCmd This point must be a direct child of the equipment. Optional (but see the tuple constraint for this report). Scalar
OaDmprMinPosSp OaDmprMinPosSp This point must be a direct child of the equipment. Optional (but see the tuple constraint for this report). Scalar
OaFlow OaFlow This point must be a direct child of the equipment. Optional (but see the tuple constraint for this report). Scalar
OaFlowMinSp OaFlowMinSp This point must be a direct child of the equipment. Optional (but see the tuple constraint for this report). Scalar
OaHumidity OaHumidity This point must be a direct child of the equipment. Optional (but see the tuple constraint for this report). Scalar
OaTemp OaTemp This point must be a direct child of the equipment. Optional (but see the tuple constraint for this report). Scalar
OffPremWeatherStation OffPremWeatherStation This point must be a direct child of the equipment. Optional (but see the tuple constraint for this report). Scalar
RaTemp RaTemp This point must be a direct child of the equipment. Optional (but see the tuple constraint for this report). Scalar
EconMode EconMode This point must be a direct child of the equipment. Optional Scalar
HtgCmd HtgCmd This point must be a direct child of the equipment. Optional Scalar
RaHumidity RaHumidity This point must be a direct child of the equipment. Optional Scalar

Rule Input Points

None

High Demand Zones Report

Summary

This report identifies the most demanding VAV boxes based on the demand for cooling and airflow within the zone, along with potential root causes. ASHRAE Energy Standard 90.1 - 2016 requires the tracking and identification of high demand zones that will likely drive reset control strategies.

Status Equipment Type Equipment Tag or Tuple Constraints  
GA vav For a given VAV to be included in the report, it must include either an ‘EffCoolSp’ input point, or an ‘EffHeatSp’ input point, or a ZoneTempDev point. If none of these points exist, then the VAV will not be included in the report.

Standard Input Points

Name Point Template Positional Requirements Optionality Multiplicity

ZoneTemp


ZoneTemp This point must be a direct child of the equipment Mandatory Scalar
EffCoolSp EffCoolSp This point must be a direct child of the equipment Optional (but see the tuple   constraint for this report) Scalar
EffHeatSp EffHeatSp This point must be a direct child of the equipment Optional (but see the tuple   constraint for this report) Scalar
ZoneTempDev ZoneTempDev This point must be a direct child of the equipment Optional (but see the tuple   constraint for this report) Scalar
DaFlow DaFlow This point must be a direct child of the equipment Optional Scalar
DaFlowSp DaFlowSp This point must be a direct child of the equipment Optional Scalar
DmprCmd DmprCmd This point must be a direct child of the equipment Optional Scalar
RhtCmd RhtCmd This point must be a direct child of the equipment Optional Scalar
DaFanSts DaFanSts This point must be a direct child of the parent AHU of the equipment. Optional Scalar

Rule Input Points

Name Rule Optionality
Rule 3.2.18.1 3.2.18.1 - VAV Discharge Airflow Sensor Failure to be applied Optional
Rule 3.2.9.1 3.2.9.1 - VAV Zone Temperature Sensor Failure to be applied Optional

OR Performance Report

Summary

This report identifies Operating Rooms (ORs) being served by Variable Air Volume boxes (VAVs) that will be evaluated and scored for compliance based on the ANSI/ASHRAE/ASHE Standard 170-2017 Ventilation of Health Care Facilities.

Status Equipment Type Equipment Tag or Tuple Constraints
Beta vav None

Standard Input Points

Name Point Template Positional Requirements Optionality Multiplicity
ZoneTemp ZoneTemp This point must be a direct child of the equipment. Mandatory Scalar
ZoneAirChangeRateTotal ZoneAirChangeRateTotal This point must be a direct child of the equipment. Mandatory Scalar
Occ Occ This point must be a direct child of the equipment. Mandatory Scalar
EconMode EconMode This point must be a direct child of the parent AHU of the equipment. Optional Scalar
OaTemp OaTemp This point must be a direct child of the parent AHU of the equipment. Optional Scalar
ZoneAirChangeRateOa ZoneAirChangeRateOa This point must be a direct child of the equipment. Optional Scalar
ZonePress ZonePress This point must be a direct child of the equipment. Optional Scalar

Rule Input Points

None

OR Scorecard Report

Summary

This report identifies Operating Rooms (ORs) being served by Variable Air Volume boxes (VAVs) that will be evaluated and scored for compliance based on the ANSI/ASHRAE/ASHE Standard 170-2017 Ventilation of Health Care Facilities.

Status Equipment Type Equipment Tag or Tuple Constraints
Beta vav None

Standard Input Points

Name Point Template Positional Requirements Optionality Multiplicity
ZoneTemp ZoneTemp This point must be a direct child of the equipment. Mandatory Scalar
ZoneAirChangeRateTotal ZoneAirChangeRateTotal This point must be a direct child of the equipment. Mandatory Scalar
Occ Occ This point must be a direct child of the equipment. Optional Scalar
ZoneAirChangeRateOa ZoneAirChangeRateOa This point must be a direct child of the equipment. Optional Scalar
ZoneHumidity ZoneHumidity This point must be a direct child of the equipment. Optional Scalar
ZonePress ZonePress This point must be a direct child of the equipment. Optional Scalar
DoorSts DoorSts This point must be a direct child of the equipment. Optional Scalar

Rule Input Points

None

IAQ Scorecard Report

Summary

This report identifies Zones being served by Variable Air Volume boxes (VAVs) will be evaluated for compliance with the latest ASHRAE and CDC guidelines for Indoor Air Quality.

Status Equipment Type Equipment Tag or Tuple Constraints
GA vav None

Standard Input Points

Name Point Template Positional Requirements Optionality Multiplicity
ZoneTemp ZoneTemp This point must be a direct child of the equipment. Mandatory Scalar
Occ Occ This point must be a direct child of the equipment. Optional Scalar
ZoneHumidity ZoneHumidity This point must be a direct child of the equipment. Optional Scalar
ZoneCO2 ZoneCO2 This point must be a direct child of the equipment. Optional Scalar
DaFlow DaFlow This point must be a direct child of the equipment. Optional Scalar
CoolMinFlow CoolMinFlow This point must be a direct child of the equipment. Optional Scalar
HeatMinFlow HeatMinFlow This point must be a direct child of the equipment. Optional Scalar
OaFlow OaFlow This point must be a direct child of parent AHU of the equipment. Optional Scalar
DaFanSts DaFanSts This point must be a direct child of parent AHU of the equipment. Optional Scalar
RaTemp RaTemp This point must be a direct child of parent AHU of the equipment. Optional Scalar
MaTemp MaTemp This point must be a direct child of parent AHU of the equipment. Optional Scalar
OaTemp OaTemp This point must be a direct child of parent AHU of the equipment. Optional Scalar
OaFlowMinSp OaFlowMinSp This point must be a direct child of parent AHU of the equipment. Optional Scalar
DaFlow DaFlow This point must be a direct child of parent AHU of the equipment. Optional Scalar
RaHumidity RaHumidity This point must be a direct child of parent AHU of the equipment. Optional Scalar
RaCO2 RaCO2 This point must be a direct child of parent AHU of the equipment. Optional Scalar

Standard Input Points

Status Rule Positional Requirements Optionality
Rule 3.1.5.1 3.1.5.1 - Outside Air Damper Does Not Meet the Minimum Position Setpoint This point must be a direct child of the parent AHU of the equipment. Optional