IAQ Scorecard Report

Overview

This report identifies zones being served by Variable Air Volume boxes (VAVs) that will be evaluated for compliance with the latest ASHRAE and CDC guidelines for Indoor Air Quality.

Intent of Report

The intent of this report is to showcase how well an air system meets indoor air quality based on temperature, humidity, and ventilation. Each of those KPIs are evaluated against CDC and ASHRAE recommendations.

Requirements

The VAV equipment type must include the following input point to appear on the report.

  • ZoneTemp

Primary Metrics

Key metrics in evaluating the operation of the equipment within the report.

  • ZoneTemp less than 68˚F or greater than 80.5˚F
  • ZoneHumidity or ReturnHumidity is less than 40% RH or greater than 60%RH
  • ZoneCo2 or ReturnCo2 is greater than 800 ppm
  • DaFlow is less than MinFlowSp
  • Parent AHU OaFlow is less than OaFlowMinSp

Input Points

To appear in a report, each piece of equipment of the appropriate type and with the appropriate equipment tag constraints must have at least one input point. There are two general categories of input points. 

Standard Input Points

A standard input point is typically a proxy point with time-series data that is retrieved at regular intervals from a remote data source such as Niagara using a Resolute Connector. Below are the Standard Input Points for the IAQ Scorecard Report.

Point Template Positional Requirements Optionality
ZoneTemp The point must be a direct child of the equipment Mandatory
CoolMinFlow The point must be a direct child of the equipment Optional
DaFanSts The point must be a direct child of the parent AHU equipment Optional
DaFlow The point must be a direct child of the equipment Optional
DaFlow The point must be a direct child of the parent AHU equipment Optional
DaFlowSp The point must be a direct child of the equipment Optional
HeatMinFlow The point must be a direct child of the equipment Optional
MaTemp The point must be a direct child of the parent AHU equipment Optional
OaFlow The point must be a direct child of the parent AHU equipment Optional
OaFlowMinSp The point must be a direct child of the parent AHU equipment Optional
OaTemp The point must be a direct child of the parent AHU equipment Optional
Occ The point must be a direct child of the equipment Optional
RaCO2 The point must be a direct child of the parent AHU equipment Optional
RaHumidity The point must be a direct child of the parent AHU equipment Optional
RaTemp The point must be a direct child of the parent AHU equipment Optional
ZoneCO2 The point must be a direct child of the equipment Optional
ZoneHumidity The point must be a direct child of the equipment Optional

Rule Input Points

A rule input point is the output of a rule applied to a given piece of equipment. It is a time series representing the presence or absence of a given fault condition. Below are the Rule Input Points for the IAQ Scorecard Report. 

Rule Name Optionality
Rule 3.1.5.1 – Outside Air Damper Does Not Meet the Minimum Position Setpoint Optional

Sample Report