Resolute Synergy™ and Fusion™ Point Template Guide
This guide details the essential equipment points necessary to generate comprehensive and robust performance reports using Resolute Synergy™ and Fusion™. Properly mapping these points ensures that the analytics and rules engine can provide insightful reports on system performance, operational efficiency, and overall building health.
NOTE: When templating damper and valve outputs, when in doubt use the command templates instead of the position template. The position is intended as a feedback point and is rarer than the command points.
Key Points Guide
Air Handling Units (AHU)
These points provide the necessary data to optimize and monitor AHU performance, ensuring energy efficiency, proper indoor air quality, and overall system reliability.
- Building Static Pressure (BldgPress)
- Point Description: Measures the pressure difference between the inside and outside of the building.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: Inches of Water Column (in. WC)
- Cooling Command (ClgCmd)
- Point Description: Command signal for cooling operation.
- Point Type: Numeric/Analog
- Assumed Range: 0-100
- Units: %
- Damper Position
- Outside Air Damper (OaDmpr)
- Point Description: Position of the outside air damper.
- Point Type: Numeric/Analog
- Assumed Range: 0-100
- Units: %
- Return Air Damper (RaDmpr)
- Point Description: Position of the return air damper.
- Point Type: Numeric/Analog
- Assumed Range: 0-100
- Units: %
- Exhaust Air Damper (EaDmpr)
- Point Description: Position of the exhaust air damper.
- Point Type: Numeric/Analog
- Assumed Range: 0-100
- Units: %
- Outside Air Damper (OaDmpr)
- Discharge Air Fan Command (DaFanCmd)
- Point Description: Command signal for the discharge air fan.
- Point Type: Boolean
- Assumed Range: 0-1 (Off/On)
- Units: Unitless
- Discharge Air Fan Frequency (DaFanFreq)
- Point Description: Frequency of the discharge air fan.
- Point Type: Numeric/Analog
- Assumed Range: 0-60
- Units: Hertz (Hz)
- Discharge Air Fan Speed (DaFanSpd)
- Point Description: Speed of the discharge air fan.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: %
- Discharge Air Fan Status (DaFanSts)
- Point Description: Status of the discharge air fan.
- Point Type: Boolean
- Assumed Range: 0-1 (Off/On)
- Units: Unitless
- Discharge Air Flow (DaFlow)
- Point Description: Measures the air flow from the discharge side.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: CFM (Cubic Feet per Minute)
- Discharge Air Humidity (DaHumidity)
- Point Description: Humidity level of the discharge air.
- Point Type: Numeric/Analog
- Assumed Range: 0-100
- Units: %RH
- Discharge Air Pressure (DaPress)
- Point Description: Pressure of the discharge air.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: in. WC
- Discharge Air Pressure Setpoint (DaPressSp)
- Point Description: Setpoint for the discharge air pressure.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: in. WC
- Discharge Air Temperature (DaTemp)
- Point Description: Temperature of the discharge air.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Discharge Air Temperature Setpoint (DaTempSp)
- Point Description: Setpoint for the discharge air temperature.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Economizer Enable (EconEnab)
- Point Description: Indicates whether the economizer is in use.
- Point Type: Boolean
- Assumed Range: 0-1 (Off/On)
- Units: Unitless
- Effective Cooling Setpoint (EffCoolSp)
- Point Description: Effective cooling setpoint for the unit.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Effective Heating Setpoint (EffHeatSp)
- Point Description: Effective heating setpoint for the unit.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Exhaust Air Flow ( EaFlow)
- Point Description: Measures the air flow of the exhaust.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: CFM
- Heating Command (HtgCmd)
- Point Description: Command signal for heating operation.
- Point Type: Numeric/Analog
- Assumed Range: 0-100
- Units: %
- Mixed Air Temp (MaTemp)
- Point Description: Temperature of the mixed air.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Occupied Cooling Setpoint (OccCoolSp)
- Point Description: Cooling setpoint when the area is occupied.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Occupied Heating Setpoint (OccHeatSp)
- Point Description: Heating setpoint when the area is occupied.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Occupied Mode (Occ)
- Point Description: Indicates whether the unit is in occupied mode.
- Point Type: Numeric
- Assumed Range: 0-1 (Off/On)
- Units: Boolean
- Outside Air Damper Command (OaDmprCmd)
- Point Description: Command signal for the outside air damper.
- Point Type: Numeric
- Assumed Range: 0-100
- Units: %
- Outside Air Damper Minimum Position Setpoint (OaDmprMinPosSp)
- Point Description: Minimum position setpoint for the outside air damper.
- Point Type: Numeric/Analog
- Assumed Range: 0-100
- Units: %
- Outside Air Damper Position (OaDmprPos)
- Point Description: Position of the outside air damper.
- Point Type: Numeric/Analog
- Assumed Range: 0-100
- Units: %
- Outside Air Flow (OaFlow)
- Point Description: Measures the airflow of the outside air.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: CFM
- Outside Air Flow Minimum Setpoint (OaFlowMinSp)
- Point Description: Minimum setpoint for the outside airflow.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: CFM
- Outside Air Humidity (OaHumidity)
- Point Description: Humidity level of the outside air.
- Point Type: Numeric/Analog
- Assumed Range: 0-100
- Units: %RH
- Outside Air Temperature (OaTemp)
- Point Description: Temperature of the outside air.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Return Air Flow (RaFlow)
- Point Description: Measures the air flow of the return air.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: CFM
- Return Air Humidity (RaHumidity)
- Point Description: Humidity level of the return air.
- Point Type: Numeric/Analog
- Assumed Range: 0-100
- Units: %RH
- Return Air Pressure (RaPress)
- Point Description: Pressure of the return air.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: in. WC
- Return Air Temperature (RaTemp)
- Point Description: Temperature of the return air.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Unoccupied Cooling Setpoint (UoccCoolSp)
- Point Description: Cooling setpoint when the area is unoccupied.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Unoccupied Heating Setpoint (UnoccHeatSp)
- Point Description: Heating setpoint when the area is unoccupied.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Zone Humidity (ZoneHumidity)
- Point Description: Humidity level within the zone.
- Point Type: Numeric/Analog
- Assumed Range: 0-100
- Units: %
- Zone Pressure (ZonePress)
- Point Description: Pressure within the zone.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: in. WC
- Zone Temperature (ZoneTemp)
- Point Description: Temperature within the zone.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Zone Temperature Setpoint (ZoneTempSp)
- Point Description: Setpoint for the zone temperature.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
Boiler Points (Blr)
These boiler points are essential for maintaining heating performance, safety, and efficiency.
- Boiler Command (BlrCmd)
- Point Description: Command signal for boiler operation.
- Point Type: Boolean
- Assumed Range: 0-1 (Off/On)
- Units: Unitless
- Boiler Leaving Setpoint (BlrLSp)
- Point Description: Setpoint for the boiler leaving temperature.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Boiler Status (BlrSts)
- Point Description: Status of the boiler.
- Point Type: Boolean
- Assumed Range: 0-1 (Off/On)
- Units: Unitless
- Entering Water Temperature (BlrETemp)
- Point Description: Temperature of the water entering the boiler.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Boiler Level (BlrLevel)
- Point Description: Command signal for heating operation.
- Point Type: Numeric/Analog
- Assumed Range: 0-100
- Units: %
- Leaving Water Temperature (BlrLTemp)
- Point Description: Temperature of the water leaving the boiler.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
Chilled Water Points
Chilled water points are critical for monitoring and controlling the cooling performance of the building.
- Chilled Water Entering Temperature (ChWETemp)
- Point Description: Temperature of the water entering the chiller.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Chilled Water Leaving Temperature (ChWLTemp)
- Point Description: Temperature of the water leaving the chiller.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Chilled Water Setpoint (ChWSp)
- Point Description: Setpoint for the chilled water temperature.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Chiller Command (ChlCmd)
- Point Description: Command signal for chiller operation.
- Point Type: Boolean
- Assumed Range: 0-1 (Off/On)
- Units: Unitless
- Chiller Status (ChlSts)
- Point Description: Status of the chiller.
- Point Type: Boolean
- Assumed Range: 0-1 (Off/On)
- Units: Unitless
- Condenser Water Entering Temperature (CndWETemp)
- Point Description: Temperature of the water entering the condenser.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Condenser Water Leaving Temperature (CndWLTemp)
- Point Description: Temperature of the water leaving the condenser.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
Cooling Tower Points
Cooling tower points are essential for managing heat rejection and maintaining optimal cooling efficiency.
- Condenser Water Circ Pump Status
- Point Description: Status of the condenser water circulation pump.
- Point Type: Boolean
- Assumed Range: 0-1 (Off/On)
- Units: Unitless
- Condenser Water Entering Temperature (CndWETemp)
- Point Description: Temperature of the water entering the cooling tower.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Condenser Water Leaving Temperature (CndWLTemp)
- Point Description: Temperature of the water leaving the cooling tower.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Condenser Water Leaving Temperature Setpoint
- Point Description: Setpoint for the condenser water leaving temperature.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Enable Command
- Point Description: Command signal to enable the cooling tower.
- Point Type: Boolean
- Assumed Range: 0-1 (Off/On)
- Units: Unitless
- Fan Speed Signal
- Point Description: Speed signal for the cooling tower fan.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: RPM
- Fan Status
- Point Description: Status of the cooling tower fan.
- Point Type: Boolean
- Assumed Range: 0-1 (Off/On)
- Units: Unitless
- Sump Temperature
- Point Description: Temperature of the water in the sump.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
Fan Coil Units (FCU)
Fan coil unit points are vital for maintaining comfort and proper temperature control within different zones.
- Cooling Command (ClgCmd)
- Point Description: Command signal for cooling operation.
- Point Type: Numeric/Analog
- Assumed Range: 0-100
- Units: %
- Effective Cooling Setpoint (EffCoolSp)
- Point Description: Effective cooling setpoint for the unit.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Effective Heating Setpoint (EffHeatSp)
- Point Description: Effective heating setpoint for the unit.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Heating Command (HtgCmd)
- Point Description: Command signal for heating operation.
- Point Type: Numeric/Analog
- Assumed Range: 0-100
- Units: %
- Occupied Cooling Setpoint (OccCoolSp)
- Point Description: Cooling setpoint when the area is occupied.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Occupied Heating Setpoint (OccHeatSp)
- Point Description: Heating setpoint when the area is occupied.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Occupied Mode
- Point Description: Indicates whether the unit is in occupied mode.
- Point Type: Boolean
- Assumed Range: 0-1 (Off/On)
- Units: Unitless
- Unoccupied Cooling Setpoint (UoccCoolSp)
- Point Description: Cooling setpoint when the area is unoccupied.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Unoccupied Heating Setpoint (UnoccHeatSp)
- Point Description: Heating setpoint when the area is unoccupied.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Zone Temperature (ZoneTemp)
- Point Description: Temperature within the zone.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Zone Temperature Setpoint (ZoneTempSp)
- Point Description: Setpoint for the zone temperature.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
Heat Pump Points
These points for heat pumps are crucial for ensuring efficient heating and cooling operations and maintaining occupant comfort.
- Effective Cooling Setpoint (EffCoolSp)
- Point Description: Effective cooling setpoint for the unit.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Effective Heating Setpoint (EffHeatSp)
- Point Description: Effective heating setpoint for the unit.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Occupied Cooling Setpoint (OccCoolSp)
- Point Description: Cooling setpoint when the area is occupied.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Occupied Heating Setpoint (OccHeatSp)
- Point Description: Heating setpoint when the area is occupied.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Occupied Mode (Occ)
- Point Description: Indicates whether the unit is in occupied mode.
- Point Type: Boolean
- Assumed Range: 0-1 (Off/On)
- Units: Unitless
- Unoccupied Cooling Setpoint (UoccCoolSp)
- Point Description: Cooling setpoint when the area is unoccupied.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Unoccupied Heating Setpoint (UnoccHeatSp)
- Point Description: Heating setpoint when the area is unoccupied.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Zone Temperature (ZoneTemp)
- Point Description: Temperature within the zone.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Zone Temperature Setpoint (ZoneTempSp)
- Point Description: Setpoint for the zone temperature.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
Meters Points
These points help track and monitor resource usage, contributing to efficient energy management and sustainability.
- Domestic Water Volume Total
- Point Description: Total accumulated volume of domestic water.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: Gallons
- Energy Total
- Point Description: Total accumulated energy consumption.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: kWh
- Gas Volume Total
- Point Description: Total accumulated volume of gas.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: Cubic Feet
Variable Air Volume (VAV) Boxes
These VAV points help in ensuring precise control over individual zones, contributing to overall building comfort and efficiency.
- Damper Command (DmprCmd)
- Point Description: Command signal for the damper.
- Point Type: Numeric/Analog
- Assumed Range: 0-100
- Units: %
- Damper Position (DaDmprPos)
- Point Description: Position of the damper in percentage.
- Point Type: Numeric/Analog
- Assumed Range: 0-100
- Units: %
- Discharge Air Fan Status (DaFanSts)
- Point Description: Status of the discharge air fan.
- Point Type: Boolean
- Assumed Range: 0-1 (Off/On)
- Units: Unitless
- Discharge Air Flow (DaFlow)
- Point Description: Measures the air flow from the discharge side.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: CFM
- Discharge Air Flow Setpoint (DaFlowSp)
- Point Description: Setpoint for the discharge air flow.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: CFM
- Discharge Air Temperature (DaTemp)
- Point Description: Temperature of the discharge air.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Effective Cooling Setpoint (EffCoolSp)
- Point Description: Effective cooling setpoint for the unit.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Effective Heating Setpoint (EffHeatSp)
- Point Description: Effective heating setpoint for the unit.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Heating Command (HtgCmd)
- Point Description: Command signal for heating operation.
- Point Type: Numeric/Analog
- Assumed Range: 0-100
- Units: %
- Occupied Cooling Setpoint (OccCoolSp)
- Point Description: Cooling setpoint when the area is occupied.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Occupied Heating Setpoint (OccHeatSp)
- Point Description: Heating setpoint when the area is occupied.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Occupied Mode (Occ)
- Point Description: Indicates whether the unit is in occupied mode.
- Point Type: Boolean
- Assumed Range: 0-1 (Off/On)
- Units: Unitless
- Reheat Command (RhtCmd)
- Point Description: Command signal for reheat operation.
- Point Type: Numeric/Analog
- Assumed Range: 0-100
- Units: %
- Return Air Flow (RaFlow)
- Point Description: Measures the air flow of the return air.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: CFM
- Unoccupied Cooling Setpoint (UoccCoolSp)
- Point Description: Cooling setpoint when the area is unoccupied.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Unoccupied Heating Setpoint (UnoccHeatSp)
- Point Description: Heating setpoint when the area is unoccupied.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Zone Air Change Rate Outside Air (ZoneAirChangeRateOa)
- Point Description: Rate of outside air changes in the zone.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: ACH (Air Changes per Hour)
- Zone Air Change Rate Total (ZoneAirChangeRateTotal)
- Point Description: Total air change rate in the zone.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: ACH
- Zone Humidity (ZoneHumidity)
- Point Description: Humidity level within the zone.
- Point Type: Numeric/Analog
- Assumed Range: 0-100
- Units: %
- Zone Pressure (ZonePress)
- Point Description: Pressure within the zone.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: in. WC
- Zone Temperature (ZoneTemp)
- Point Description: Temperature within the zone.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Zone Temperature Deviation (ZoneTempDev)
- Point Description: Deviation from the setpoint temperature within the zone.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F
- Zone Temperature Setpoint (ZoneTempSp)
- Point Description: Setpoint for the zone temperature.
- Point Type: Numeric/Analog
- Assumed Range: Varies
- Units: °F