3.1.1.1 - 3.1.19.1 AHU Rules

3.1.1.1 - AHU Simultaneous Heating and Cooling

Summary

This unit is heating and cooling at the same time.

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Cooling Command ClgCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Heating Command HtgCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 15 The delay represents a span of time in minutes during which the ahu must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Cooling Command Threshold Numeric 1 This number is the cooling command threshold indicating the command is “On.” If the ahu’s cooling command is greater than or equal to the cooling command threshold at the same time the ahu’s heating command is greater than or equal to the heating command threshold for a period longer than the delay in order for a fault condition to exist.
Heating Command Threshold Numeric 1 This number is the heating command threshold indicating the command is “On.” If the ahu’s heating command is greater than or equal to the heating command threshold at the same time the ahu’s cooling command is greater than or equal to the cooling command threshold for a period longer than the delay in order for a fault condition to exist.

3.1.3.1 - Free Cooling is not Maximized

Summary

Free Cooling is not being fully utilized. Mechanical cooling is being used and the outside air damper is not fully open. The economizer should be used as the first stage of cooling.

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Temperature OaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Damper Command (open/closed) OaDmprCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Cooling Command ClgCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 30 The delay represents a span of time in minutes during which the ahu must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Economizer Outside Air Enable Setpoint Numeric 67 This number (in Fahrenheit) is the maximum allowed value of the outside air temperature. The entering outside air temperature must exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Outside Air Damper High Setpoint Numeric 95 This number (in Fahrenheit) is the maximum allowed value of the outside air temperature. The entering outside air temperature must exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Cooling Command Minimum Numeric 1 This number (in Fahrenheit) is the minimum allowed value of the cooling command. The cooling command must exceed or be equal to the cooling command minimum for a period longer than the delay in order for a fault condition to exist.

3.1.4.1 - Outside Air Damper Position is Greater Than Minimum Setpoint During Heating Mode

Summary

Excess outside air is being brought into the building. The Outside Air Damper is greater than the minimum position setpoint.

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Outside Air Temperature OaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Damper Command (open/closed) OaDmprCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Discharge Air Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Cooling Command ClgCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Heating Command HtgCmd This point must be a direct child of the equipment that the rule is attached to. Optional Scalar
Outside Air Damper Minimum Position Setpoint OaDmprMinPosSp This point must be a direct child of the equipment that the rule is attached to. Optional Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 30 The delay represents a span of time in minutes during which the ahu must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Economizer Outside Air Temperature Setpoint Numeric 70 This number (in Fahrenheit) is the maximum allowed value of the outside air temperature. The entering outside air temperature must exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Outside Air Damper Minimum Position Setpoint Numeric 20 This number is the minimum outside air damper position needed for ventilation when an ahu is operating.
Outside Air Damper Position Threshold Numeric 5 The outside air damper position must be greater than the minimum position setpoint by this amount (in percent command) for a fault condition to exist.
Cooling Command Limit Numeric 1 This number is the cooling command threshold indicating the command is “On.” If the ahu’s cooling command is greater than or equal to the cooling command threshold at the same time the ahu’s heating command is greater than or equal to the heating command threshold for a period longer than the delay then a Fault is generated.

3.1.4.2 - Outside Airflow is Greater Than Minimum Setpoint During Heating Mode

Summary

Excess outside air is being brought into the building. The outside airflow is greater than the outside airflow minimum position setpoint.

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Outside Air Temperature OaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Cooling Command ClgCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Heating Command HtgCmd This point must be a direct child of the equipment that the rule is attached to. Optional Scalar
Outside Air Flow OaFlow This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Flow Minimum Setpoint OaFlowMinSp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 30 The delay represents a span of time in minutes during which the ahu must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Cooling Command Limit Numeric 1 This number is the cooling command threshold indicating the command is “On.” If the ahu’s cooling command is greater than or equal to the cooling command threshold at the same time the ahu’s heating command is greater than or equal to the heating command threshold for a period longer than the delay in order for a fault condition to exist.
Heating Command Limit Numeric 1 This number is the heating command threshold indicating the command is “On.” If the ahu’s heating command is greater than or equal to the heating command threshold at the same time the ahu’s cooling command is greater than or equal to the cooling command threshold for a period longer than the delay in order for a fault condition to exist.
Outside Airflow Threshold Numeric 500 This number (in cfm) is the outside airflow threshold.  The outside airflow must exceed the outside airflow minimum setpoint added to the outside airflow threshold for a period longer than the delay in order for a fault condition to exist.
Economizer Outside Air Temperature Setpoint Numeric 70 This number (in Fahrenheit) is the maximum allowed value of the outside air temperature. The entering outside air temperature must exceed this threshold for a period longer than the delay in order for a fault condition to exist.

3.1.4.3 - Outside Air Damper Position is Greater Than Minimum Setpoint During Mechanical Cooling Mode

Summary

Excess outside air is being brought into the building. The Outside Air Damper is greater than the minimum position setpoint during mechanical cooling mode. 

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu --

1. OaTemp associated with this equipment

2. OaTemp at the building level (on prem)

3. OaTemp of the off prem weather station

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Da Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Damper Command (open/closed) OaDmprCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Damper Minimum Position Setpoint OaDmprMinPosSp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Cooling Command ClgCmd This point must be a direct child of the equipment that the rule is attached to Mandatory Scalar
Heating Command HtgCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Temperature Oatemp This point must be a direct child of the equipment that the rule is attached to Optional Scalar
Outside Air Temperature OaTemp This point must be a direct child of the equipment that the rule is attached to. Point u son prem at the building level.  Optional Scalar
Outside Air Temperature OaTemp This point must be a direct child of the equipment that the rule is attached to. Point is off prem at weather station. Optional Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 30 The delay represents a span of time in minutes during which the ahu must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Economy Outside Air Temperature Setpoint Numeric 70 The economy outside air temp setpoint. The outside air temperature must be greater than this constant for a period longer than delay in order for a fault to exist.
Outside Air Damper Position Numeric 0 The position of the outside air damper. The outside air damper position plus this constant must be less than the outside air damper command for a period longer than delay in order for a fault to exist.
Cooling Command Numeric 0 The cooling command. The cooling command must be greater than this constant for a period longer than delay in order for a fault to exist.
Heating Command Numeric 0 The heating command. The heating command must be equal to than this constant for a period longer than delay in order for a fault to exist.

3.1.4.4 - Outside Airflow is Greater Than Minimum Setpoint During Mechanical Cooling Mode

Summary

Excess outside air is being brought into the building. The outside airflow is greater than the outside airflow minimum setpoint during mechanical cooling mode. 

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu --

OaTemp

OaTempOnPremWS

OaTemoOffPremWS

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
DA Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Damper Command (open/closed) OaDmprCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Damper Minimum Position Setpoint OaDmprMinPosSp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Cooling Command ClgCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Heating Command HtgCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Temperature OaTemp This point must be a direct child of the equipment that the rule is attached to. Optional Scalar
Outside Air Temperature OaTemp This point must be a direct child of the equipment that the rule is attached to. Point is off prem at weather station. Optional Scalar
Outside Air Temperature OaTemp This point must be a direct child of the equipment that the rule is attached to. Point is off prem at weather station. Optional Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 30 The delay represents a span of time in minutes during which the ahu must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Economy Outside Air Temperature Setpoint Numeric

70


The economy outside air temp setpoint. The outside air temperature must be greater than this constant for a period longer than delay in order for a fault to exist.
Outside Air Percent Numeric 0 The outside air percent. The outside air flow must be greater than this constant plus 100 and divided by 100 for a period longer than delay in order for a fault to exist.
Cooling Command Numeric 0 The cooling command. The cooling command must be greater than this constant for a period longer than delay in order for a fault to exist. 
Heating Command Numeric 0 The heating command. The heating command must be equal to this constant for a period longer than delay in order for a fault to exist. 

3.1.5.1 - Outside Air Damper Does Not Meet the Minimum Position Setpoint

Summary

The outside air damper is less than the minimum position setpoint and sufficient ventilation may not be provided.

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Damper Command (open/closed) OaDmprCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Damper Minimum Position Setpoint OaDmprMinPosSp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Mixed Air Temperature MaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 60 The delay represents a span of time in minutes during which the ahu must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Mixed Air Temperature Low Limit Setpoint Numeric 40 This number (in Fahrenheit) is the minimum allowed value of mixed air temperature. The mixed air temperature must exceed this threshold for a period longer than the delay in order for a fault condition to exist.

3.1.6.1 - Percent Outside Air Calculated is Greater Than Outside Air Damper Command

Summary

Excess outside air is being brought into the building, increasing heating and cooling costs. The calculated outside air percent is greater than the outside air damper command plus a threshold. Calculated OA% = 100 X [(RaTemp-MaTemp) / (RaTemp-OaTemp)].

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Return Air Temperature RaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Mixed Air Temperature MaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Temperature OaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Damper Command (open/closed) OaDmprCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 60 The delay represents a span of time in minutes during which the ahu must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Damper Position Threshold Numeric 15 This number (as a percentage) is the damper position threshold.  The value of mixed air temperature subtracted from the return air temperature times 100 divided by outside air temperature subtracted from the  return air temperature must exceed the value of outside air damper command added to the damper position threshold for a period longer than the delay in order for a fault condition to exist.

3.1.6.2 - Outside Air Fraction is Too High Compared to Minimum Outside Airflow Setpoint

Summary

Outside air fraction too high; should equal %OA min during heating and cooling operating state.

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu --

OaTemp

OaTempOnPremWS

OaTempOffPremWS

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Return Air Temperature RaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Mixed Air Temperature MaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Temperature OaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Heating Command HtgCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Cooling Command ClgCmd i This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 15 The delay represents a span of time in minutes during which the ahu must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Minimum Temperature Differential Numeric 10 Minimum temperature differential threshold. This constant must be less than or equal to the absolute value of return air temp minus outside air temp for a period longer than delay in order for a fault to exist.
Airflow Error Threshold Numeric 30 Airflow error threshold.
Minimum Outside Air Percentage Threshold Numeric 20 Minimum outside air percentage threshold.
Heating Command Numeric 0 Heating command threshold. This constant must be less than the heating command for a period longer than delay in order for a fault to exist.
Cooling Command Numeric 0 Cooling command threshold. This constant must be less than the cooling command for a period longer than delay in order for a fault to exist.

3.1.7.1 - Percent Outside Air Calculated is Less Than Outside Air Damper Command

Summary

The calculated outside air percent is less than the outside air damper command minus a threshold, indicating the actual damper position is less than the command. Calculated OA% = 100 X (RaTemp-MaTemp) / (RaTemp-OaTemp)

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Return Air Temperature RaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Mixed Air Temperature MaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Temperature OaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Damper Command (open/closed) OaDmprCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 60 The delay represents a span of time in minutes during which the ahu must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Damper Position Threshold Numeric 15 This number (as a percentage) is the damper position threshold.  The value of mixed air temperature subtracted from the return air temperature times 100 divided by outside air temperature subtracted from the  return air temperature must not exceed the value of outside air damper command added to the damper position threshold for a period longer than the delay in order for a fault condition to exist.

3.1.7.2 - Outside Air Fraction is Too Low Compared to Minimum Outside Airflow Setpoint

Summary

Outside air fraction too low; should equal %OA min during Heating or Mechanical Cooling Operating State

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu --

OaTemp

OaTempOnPremWS

OaTempOffPremWS

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Return Air Temperature RaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Mixed Air Temperature MaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Temperature OaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Heating Command HtgCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Cooling Command ClgCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 15 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Minimum Temperature Differential Threshold Numeric 10 Minimum temperature differential threshold. This constant must be less than or equal to the absolute value of return air temp minus outside air temp for a period longer than delay in order for a fault to exist.
Airflow Error Threshold Numeric 30 Airflow error threshold.
Minimum Outside Air Percentage Threshold Numeric 20 Minimum outside air percentage threshold.
Heating Command Numeric 0 Heating command threshold. This constant must be less than the heating command for a period longer than delay in order for a fault to exist.
Cooling Command Numeric 0 Cooling command threshold. This constant must be less than the cooling command for a period longer than delay in order for a fault to exist.

3.1.7.3 - Outside Airflow is Less Than Minimum Setpoint During Heating Mode

Summary 

Less outside air is being brought into the building than what is required by code. The outside airflow is less than the outside airflow minimum setpoint during heating mode. 

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Flow OaFlow This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Flow Minimum Setpoint
This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Heating Command HtgCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Cooling Command ClgCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 30 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Outside Airflow Percentage Threshold Numeric 10 Minimum temperature differential threshold. This constant must be less than or equal to the absolute value of return air temp minus outside air temp for a period longer than delay in order for a fault to exist.
Cooling Command Threshold Numeric 30 Airflow error threshold.
Heating Command Threshold Numeric 20 Minimum outside air percentage threshold.

3.1.7.4 - Outside Airflow is Less Than Minimum Setpoint During Cooling Mode

Summary

Less outside air is being brought into the building than what is required by code. The outside airflow is less than the outside airflow minimum setpoint during cooling mode. 

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air Fan Status DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Flow OaFlow This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Outside Air Flow Minimum Setpoint OaFlowMinSp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Cooling Command ClgCmd This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Heating Command  HtgCmd This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 30 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Outside Airflow Percentage Threshold Numeric 10
Cooling Command Threshold Numeric 0
Heating Command Threshold Numeric 0

3.1.8.1 - Operating Outside of Schedule

Summary

The air handling unit is operating outside of the defined occupied schedule. 

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- DaFanSts || DaFanCmd

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Return Air Temperature  DaTemp This point must be a direct child of the equipment that the rule is attached to. Optional Scalar
Discharge Air Fan Status DaFanSts This point must be a direct child of the equipment that the rule is attached to.  Optional Scalar
Discharge Air Fan Command DaFanCmd This point must be a direct child of the equipment that the rule is attached to.  Optional Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 120 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Sunday Schedule Start Time Numeric 8
Sunday Schedule Stop Time Numeric 12
Saturday Schedule Start Time Numeric 8
Saturday Schedule Stop Time Numeric 16
Weekday Schedule Start Time Numeric 6
Weekday Schedule Stop Time Numeric 18
Unoccupied Heating Temperature Setpoint Numeric 62
Unoccupied Cooling Temperature Setpoint Numeric 80

3.1.9.1 - Discharge Air Temperature Sensor Failure

Summary

The temperature sensory point does not change by more than a tolerance of (0.01) or is outside the range (250 - -40).

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air Temperature  DaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 120 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
High Threshold Numeric 250 This number (in Fahrenheit) is the maximum allowed value of the discharge air temperature. The discharge air temperature must exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Low Threshold Numeric -40 This number (in Fahrenheit) is the minimum allowed value of the discharge air temperature. The discharge air temperature must not exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Variance Threshold Numeric 0.01 This number (in Fahrenheit) is the variance threshold.  The difference value of the high threshold and low threshold must not exceed the variance threshold for a period longer than the delay in order for a fault condition to exist.

3.1.9.2 - Mixed Air Temperature Sensor Failure

Summary

The temperature sensor point does not change by more than a tolerance of (0.01) or is outside the range (150 - -40).

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Mixed Air Temperature MaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 120 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
High Threshold Numeric 150 This number (in Fahrenheit) is the maximum allowed value of the mixed air temperature. The mixed air temperature must exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Low Threshold Numeric -40 This number (in Fahrenheit) is the minimum allowed value of the mixed air temperature. The mixed air temperature must not exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Variance Threshold Numeric 0.01 This number (in Fahrenheit) is the variance threshold.  The difference value of the high threshold and low threshold must not exceed the variance threshold for a period longer than the delay in order for a fault condition to exist.

3.1.9.3 - Return Air Temperature Sensor Failure

Summary

The temperature sensor point does not change by more than a tolerance of (0.01) or is outside the range (130 - 20).

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Return Air Temperature RaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 120 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
High Threshold Numeric 130 This number (in Fahrenheit) is the maximum allowed value of the return air temperature. The return air temperature must exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Low Threshold Numeric 20 This number (in Fahrenheit) is the minimum allowed value of the return air temperature. The return air temperature must not exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Variance Threshold Numeric 0.01 This number (in Fahrenheit) is the variance threshold.  The difference value of the high threshold and low threshold must not exceed the variance threshold for a period longer than the delay in order for a fault condition to exist.

3.1.9.4 - Outside Air Temperature Sensor Failure

Summary

The temperature sensor point does not change by more than a tolerance of (0.01) or is outside the range (130 - -60).

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Outside Air Temperature OaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 120 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
High Threshold Numeric 130 This number (in Fahrenheit) is the maximum allowed value of the outside air temperature. The outside air temperature must exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Low Threshold Numeric -60 This number (in Fahrenheit) is the minimum allowed value of the outside air temperature. The outside air temperature must not exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Variance Threshold Numeric 0.01 This number (in Fahrenheit) is the variance threshold.  The difference value of the high threshold and low threshold must not exceed the variance threshold for a period longer than the delay in order for a fault condition to exist.

3.1.9.5 - Zone Temperature Sensor Failure

Summary

The zone temperature sensor has failed. The temperature sensor point is invariant or is outside the expected range.

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Zone Temperature ZoneTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 120 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
High Threshold Numeric 150 This number (in Fahrenheit) is the maximum allowed value of the zone temperature. The zone temperature must exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Low Threshold Numeric 30 This number (in Fahrenheit) is the minimum allowed value of the zone temperature. The zone temperature must not exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Variance Threshold Numeric 0.01 This number (in Fahrenheit) is the variance threshold.  The difference value of the high threshold and low threshold must not exceed the variance threshold for a period longer than the delay in order for a fault condition to exist.

3.1.10.1 - Discharge Air Pressure Sensor Failure

Summary

The pressure sensor point does not change by more than a tolerance of (0.001) or is outside the range (7.0 - -2.0).

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air Pressure DaPress This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Discharge Air Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 60 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
High Threshold Numeric 7.0 This number (in inches of water) is the maximum allowed value of the discharge air pressure. The discharge air pressure must exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Low Threshold Numeric -2.0 This number (in inches of water) is the minimum allowed value of the discharge air pressure. The discharge air pressure must not exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Variance Threshold Numeric 0.001 This number (in inches of water) is the variance threshold.  The difference value of the high threshold and low threshold must not exceed the variance threshold for a period longer than the delay in order for a fault condition to exist.

3.1.10.2 - Building Air Pressure Sensor Failure

Summary

The pressure sensor point does not change by more than a tolerance of (0.001) or is outside the range (1.0 - -1.0).

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Building Static Pressure BldgPress This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Discharge Air Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 60 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
High Threshold Numeric 1.0 This number (in inches of water) is the maximum allowed value of the building static pressure. The building static pressure must exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Low Threshold Numeric -1.0 This number (in inches of water) is the minimum allowed value of the building static pressure. The building static pressure must not exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Variance Threshold Numeric 0.001 This number (in inches of water) is the variance threshold.  The difference value of the high threshold and low threshold must not exceed the variance threshold for a period longer than the delay in order for a fault condition to exist.

3.1.10.3 - Return Air Pressure Sensor Failure

Summary

The pressure sensor point does not change by more than a tolerance of (0.001) or is outside the range (5.0 - -3.0).

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Return Air Pressure RaPress This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 60 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
High Threshold Numeric 5.0 This number (in inches of water) is the maximum allowed value of the return air pressure. The return air pressure must exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Low Threshold Numeric -3.0 This number (in inches of water) is the minimum allowed value of the return air pressure. The return air pressure must not exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Variance Threshold Numeric 0.001 This number (in inches of water) is the variance threshold.  The difference value of the high threshold and low threshold must not exceed the variance threshold for a period longer than the delay in order for a fault condition to exist.

3.1.10.4 - Zone Pressure Sensor Failure

Summary

The pressure sensor point does not change by more than a tolerance of (0.001) or is outside the range (1.0 - -1.0).

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Zone Pressure ZonePress This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 60 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
High Threshold Numeric 1.0 This number (in inches of water) is the maximum allowed value of the zone pressure. The zone pressure must exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Low Threshold Numeric -1.0 This number (in inches of water) is the minimum allowed value of the zone pressure. The zone must not exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Variance Threshold Numeric 0.001 This number (in inches of water) is the variance threshold.  The difference value of the high threshold and low threshold must not exceed the variance threshold for a period longer than the delay in order for a fault condition to exist.

3.1.11.1 - Discharge Air Humidity Sensor Failure

Summary

The humidity sensor point does not change by more than a tolerance of (0.001) or is outside the range (100 - 0).

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air Humidity DaHumidity This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 120 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
High Threshold Numeric 100 This number (as a percentage) is the maximum allowed value of the discharge air humidity. The discharge air humidity must exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Low Threshold Numeric 0 This number (as a percentage) is the minimum allowed value of the discharge air humidity. The discharge air humidity must not exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Variance Threshold Numeric 0.001 This number is the variance threshold.  The difference value of the high threshold and low threshold must not exceed the variance threshold for a period longer than the delay in order for a fault condition to exist.

3.1.11.2 - Return Air Humidity Sensor Failure

Summary

The humidity sensor point does not change by more than a tolerance of (0.001) or is outside the range (100 - 0).

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Return Air Humidity RaHumidity This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 120 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
High Threshold Numeric 100 This number (as a percentage) is the maximum allowed value of the return air humidity. The return air humidity must exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Low Threshold Numeric 0 This number (as a percentage) is the minimum allowed value of the return air humidity. The return air humidity must not exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Variance Threshold Numeric 0.001 This number is the variance threshold.  The difference value of the high threshold and low threshold must not exceed the variance threshold for a period longer than the delay in order for a fault condition to exist.

3.1.11.3 - Outside Air Humidity Sensor Failure

Summary

The humidity sensor point does not change by more than a tolerance of (0.001) or is outside the range (100 - 0).

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Outside Air Humidity OaHumidity This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 120 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
High Threshold Numeric 100 This number (as a percentage) is the maximum allowed value of the outside air humidity. The outside air humidity must exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Low Threshold Numeric 0 This number (as a percentage) is the minimum allowed value of the outside air humidity. The outside air humidity must not exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Variance Threshold Numeric 0.001 This number is the variance threshold.  The difference value of the high threshold and low threshold must not exceed the variance threshold for a period longer than the delay in order for a fault condition to exist.

3.1.11.4 - Zone Humidity Sensor Failure

Summary

The humidity sensor point does not change by more than a tolerance of (0.001) or is outside the range (100 - 0).

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Zone Humidity ZoneHumidity This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 120 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
High Threshold Numeric 100 This number (as a percentage) is the maximum allowed value of the zone humidity. The zone humidity must exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Low Threshold Numeric 0 This number (as a percentage) is the minimum allowed value of the zone humidity. The zone humidity must not exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Variance Threshold Numeric 0.001 This number is the variance threshold.  The difference value of the high threshold and low threshold must not exceed the variance threshold for a period longer than the delay in order for a fault condition to exist.

3.1.12.1 - Discharge Airflow Sensor Failure

Summary

The discharge airflow sensor has failed. The airflow sensor point is invariant or is outside the expected range.

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Discharge Air Flow DaFlow This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 30 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
High Threshold Numeric 150,000 This number (in cfm) is the maximum allowed value of the discharge airflow. The discharge airflow must exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Low Threshold Numeric 20 This number (in cfm) is the minimum allowed value of the discharge airflow. The discharge airflow must not exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Variance Threshold Numeric 1.0 This number (in cfm) is the variance threshold.  The difference value of the high threshold and low threshold must not exceed the variance threshold for a period longer than the delay in order for a fault condition to exist.

3.1.12.2 – Return Airflow Sensor Failure

Summary

The return airflow sensor has failed. The airflow sensor point is invariant or is outside the expected range.

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Return Air Flow RaFlow This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 30 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
High Threshold Numeric 150,000 This number (in cfm) is the maximum allowed value of the return airflow. The return airflow must exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Low Threshold Numeric 20 This number (in cfm) is the minimum allowed value of the return airflow. The return airflow must not exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Variance Threshold Numeric 1.0 This number (in cfm) is the variance threshold.  The difference value of the high threshold and low threshold must not exceed the variance threshold for a period longer than the delay in order for a fault condition to exist.

Rule 3.1.12.3 - Outside Airflow Sensor Failure

Summary

The outside airflow sensor has failed. The airflow sensor point is invariant or is outside the expected range.

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Flow OaFlow This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 30 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
High Threshold Numeric 150,000 This number (in cfm) is the maximum allowed value of the outside airflow. The outside airflow must exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Low Threshold Numeric 20 This number (in cfm) is the minimum allowed value of the outside airflow. The outside airflow must not exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Variance Threshold Numeric 1.0 This number (in cfm) is the variance threshold.  The difference value of the high threshold and low threshold must not exceed the variance threshold for a period longer than the delay in order for a fault condition to exist.

3.1.12.4 - Exhaust Airflow Sensor Failure

Summary

The exhaust airflow sensor has failed. The airflow sensor point is invariant or is outside the expected range.

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Exhaust Air Flow EaFlow This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 30 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
High Threshold Numeric 150,000 This number (in cfm) is the maximum allowed value of the exhaust airflow. The exhaust airflow must exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Low Threshold Numeric 20 This number (in cfm) is the minimum allowed value of the exhaust airflow. The exhaust airflow must not exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Variance Threshold Numeric 1.0 This number (in cfm) is the variance threshold.  The difference value of the high threshold and low threshold must not exceed the variance threshold for a period longer than the delay in order for a fault condition to exist.

3.1.13.1 - Discharge Air Temperature Setpoint Could Be Raised

Summary

All zones served by this air handling unit are in a heating or minimum cooling mode, zone temperature is being met, and return air humidity (if available) is at or below return air high relative humidity setpoint, indicating the discharge air temperature setpoint could be raised. 

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air   Fan Status  DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Reheat Command RhtCmd This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Discharge Air Flow Setpoint DaFlowSp This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Discharge Air Flow Minimum Setpoint DaFlowMinSp This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Discharge Air Flow Maximum Setpoint DaFlowMaxSp This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Effective Cooling Setpoint EffCoolSp This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Occupied Cooling Setpoint OccCoolSp This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Zone Temperature Setpoint ZoneTempSp This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Return Air Humidity RaHumidity This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Return Air High Humidity Setpoint RaHighHumiditySp This point must be a direct child of the equipment that the rule is attached to.  Optional Vector

Input Constants

Name Data Type Default Value Description
Delay Numeric 60 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Zone Temperature Threshold Numeric 0.5

3.1.13.2 - Discharge Air Temperature Setpoint Could be Lowered

Summary

One or more zones served by this air handling unit are at a 100% cooling mode and zone temperature is not being met, or return air humidity (if available) is above return air high relative humidity setpoint, indicating the discharge air temperature setpoint could be lowered. 

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air   Fan Status  DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Cooling Command ClgCmd This point must be a direct child of the equipment that the rule is attached to. 

Reheat Command RhtCmd This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Discharge Air Flow Setpoint DaFlowSp This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Zone Temperature ZoneTemp This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Discharge Air Flow Maximum Setpoint DaFlowMaxSp This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Effective Cooling Setpoint EffCoolSp This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Occupied Cooling Setpoint OccCoolSp This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Zone Temperature Setpoint ZoneTempSp This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Return Air Humidity RaHumidity This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Return Air High Humidity Setpoint RaHighHumiditySp This point must be a direct child of the equipment that the rule is attached to.  Optional Vector

Input Constants

Name Data Type Default Value Description
Delay Numeric 15 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Zone Temperature Threshold Numeric 0.5
Maximum Cooling Command Threshold Numeric 90

3.1.14.1 - Discharge Air Fan VFD Invariant

Summary

The discharge air fan VFD is invariant and may be overridden or in Hand.

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Discharge Air Fan Speed (single or common) DaFanSpd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Discharge Air Pressure DaPress This point must be a direct child of the equipment that the rule is attached to. Optional Scalar
Discharge Air Pressure Setpoint DaPressSp This point must be a direct child of the equipment that the rule is attached to. Optional Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 60 The delay represents a span of time in minutes during which the fan must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Maximum VFD Speed Numeric 99 This number (as a percentage) is the maximum allowed value of the discharge fan VFD speed. The discharge fan VFD speed must not exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Pressure Setpoint Threshold Numeric 0.1 This number (in inches of water) is the minimum allowed value of the discharge air pressure. The discharge air pressure must exceed this threshold added to the discharge air pressure setpoint or the discharge air pressure must not exceed this threshold subtracted from the discharge air pressure setpoint for a period longer than the delay in order for a fault condition to exist.
Variance Threshold Numeric 1.0 This number is compared to the value of the difference between the maximum discharge air fan speed and the minimum discharge air fan speed. The difference value must not exceed the variance threshold for a period longer than the delay in order for a fault condition to exist.

3.1.14.2 - Discharge Air Fan VFD Invariant

Summary:

The discharge air fan VFD is invariant and may be overridden or in Hand.

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Discharge Air Fan Frequency (single or common) DaFanFreq This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Discharge Air Pressure DaPress This point must be a direct child of the equipment that the rule is attached to. Optional Scalar
Discharge Air Pressure Setpoint DaPressSp This point must be a direct child of the equipment that the rule is attached to. Optional Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 60 The delay represents a span of time in minutes during which the fan must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Maximum VFD Frequency Numeric 58 This number (in Hz) is the maximum allowed value of the discharge fan VFD frequency. The discharge fan VFD frequency must not exceed this threshold for a period longer than the delay in order for a fault condition to exist.
Pressure Setpoint Threshold Numeric 0.1 This number (in inches of water) is the minimum allowed value of the discharge air pressure. The discharge air pressure must exceed this threshold added to the discharge air pressure setpoint or the discharge air pressure must not exceed this threshold subtracted from the discharge air pressure setpoint for a period longer than the delay in order for a fault condition to exist.
Variance Threshold Numeric 0.1 This number is compared to the value of the difference between the maximum discharge air fan speed and the minimum discharge air fan speed. The difference value must not exceed the variance threshold for a period longer than the delay in order for a fault condition to exist.

3.1.15.1 - Discharge Fan Static Pressure Setpoint is Greater Than High Limit

Summary

The discharge fan static pressure setpoint is greater than the high limit and may be overridden. Excessively high fan static pressure increases fan energy and operating costs. ASHRAE Energy Standard 90.1 2016, section 6.5.3.2.2 VAV Static Pressure Sensor Location, limits the static pressure setpoint to 1.2 in. of water.

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Discharge Air Pressure Setpoint DaPressSp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 30 The delay represents a span of time in minutes during which the fan must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
High Static Pressure Limit Numeric 2 This number (in inches of water) is the maximum allowed value of the discharge fan static pressure. The discharge fan static pressure must exceed this threshold for a period longer than the delay in order for a fault condition to exist.

3.1.16.1 - Discharge Fan Static Pressure is Greater Than Setpoint

Summary

The discharge fan static pressure is greater than the static pressure setpoint and may be overridden or experiencing inefficient control, increasing fan energy and operating costs.

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Discharge Air Pressure DaPress This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Discharge Air Pressure Setpoint DaPressSp This point must be a direct child of the equipment that the rule is attached to. Optional Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 30 The delay represents a span of time in minutes during which the fan must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Static Pressure Threshold Numeric 0.15 This number (in inches of water) is the maximum allowed value of the discharge fan pressure. The discharge fan pressure must exceed this threshold added to the discharge air pressure setpoint or the discharge fan pressure must exceed this threshold added to the default static pressure setpoint for a period longer than the delay in order for a fault condition to exist.
Default Static Pressure Setpoint Numeric 2.0 This number (in inches of water) is the default value of the discharge fan static pressure setpoint. The discharge fan pressure must exceed this threshold added to the default static pressure setpoint for a period longer than the delay in order for a fault condition to exist.

3.1.17.1 - Discharge Fan Static Pressure is Less Than Setpoint

Summary

The discharge fan static pressure is less than the static pressure setpoint and may be experiencing inefficient control or mechanical failure, and may lead to comfort complaints.

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Discharge Air Pressure DaPress This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Discharge Air Pressure Setpoint DaPressSp This point must be a direct child of the equipment that the rule is attached to. Optional Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 30 The delay represents a span of time in minutes during which the fan must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Static Pressure Threshold Numeric 0.25 This number (in inches of water) is the maximum allowed value of the discharge fan pressure. The discharge fan pressure must not exceed this threshold subtracted from the discharge air pressure setpoint or the discharge fan pressure must not exceed this threshold subtracted from the default static pressure setpoint for a period longer than the delay in order for a fault condition to exist.
Default Static Pressure Setpoint Numeric 0.6 This number (in inches of water) is the default value of the discharge fan pressure setpoint. The discharge fan pressure must not exceed this threshold subtracted from the default static pressure setpoint for a period longer than the delay in order for a fault condition to exist.

3.1.17.2 - Low Cold and Hot Deck Static Pressure

Summary

When the cold and hot deck static pressure is less than a maximum error allowed. 

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air Fan Status DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Cold Deck Static Pressure ColdDeckStPrs This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Cold Deck Static Pressure Setpoint ColdDeckStPrsSp This point must be a direct child of the equipment that the rule is attached to.  Optional Scalar
Hot Deck Static Pressure Setpoint HotDeckStPrsSp This point must be a direct child of the equipment that the rule is attached to.  Optional Scalar
Hot Deck Static Pressure  HotDeckStPrs This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 30 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Cold Deck Static Pressure Threshold Numeric 0.15
Hot Deck Static Pressure Threshold Numeric 0.15
Default Cold Deck Static Pressure Setpoint Numeric 2.0
Default Hot Deck Static Pressure Setpoint Numeric 2.0

3.1.19.1 Outside Damper Open When Unit is Off

Summary

The outside air damper is open and the supply fan is off, allowing air infiltration. The damper should be shut when the unit is off.

Equipment Type Equipment Tag Constraints Tuple Constraints
ahu -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Discharge Air Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Damper Command (open/closed) OaDmprCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 15 The delay represents a span of time in minutes during which the damper must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Did this answer your question? Thanks for the feedback There was a problem submitting your feedback. Please try again later.

Still need help? Contact Us Contact Us