2.4 Heat Exchanger and 2.5 Chilled Water Plant Rules

2.4 Heat Exchangers

2.4.1.1 - Primary Chilled Water Heat Exchanger Leaving Temperature Sensor Failure

Summary

The primary chilled water heat exchanger leaving chilled water temperature sensor has failed. The temperature sensor point is invariant or is outside the expected range.

Equipment Type Equipment Tag Constraints Tuple Constraints
heatExchanger -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Condenser Water Leaving Temperature CWLTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Chilled Water Setpoint ChWSp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Chilled Water Leaving Temperature ChWLTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Heat Exchanger Condenser Water Isolation Valve Command  HXCWIsoVlvCmd This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Heat Exchanger Chilled Water Isolation Valve Command HXChWIsoVlvCmd This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar

Input Constants

Name Data Type Default Value Description

Delay


Numeric 15 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
High Threshold Numeric 70 MAX_VALUE
Low Threshold Numeric 20 MIN_VALUE
Variance Threshold Numeric 0.01
Heat Exchanger Design Approach Numeric 2

2.4.2.1 - Primary Chilled Water Heat Exchanger Entering Temperature Sensor Failure

Summary

The primary chilled water heat exchanger entering chilled water temperature sensor has failed. The temperature sensor point is invariant or is outside the expected range. 

Equipment Type Equipment Tag Constraints Tuple Constraints
heatExchanger -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Heat Exchanger Condenser Water Isolation Valve Command HXCWIsoVlvCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Heat Exchanger Chilled Water Isolation Valve Command HXChWIsoVlvCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Condenser Water Leaving Temperature CWLTemp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Chilled Water Entering Temperature ChWETemp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Chilled Water Setpoint ChWSp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar

Input Constants

Name Data Type Default Value Description

Delay


Numeric 15 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
High Threshold Numeric 70 MAX_VALUE
Low Threshold Numeric 20 MIN_VALUE
Variance Threshold Numeric 0.01
Heat Exchanger Design Approach Numeric 2

2.4.3.1 - Heat Exchanger Chilled Water Isolation Valve is Open When Condenser Water Location Valve is Closed

Summary

Isolation valves on both sides of the heat exchanger should either be both open or closed. 

Equipment Type Equipment Tag Constraints Tuple Constraints
heatExchanger -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Heat Exchanger Chilled Water Isolation Valve Command HXChWIsoVlvCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Heat Exchanger Condenser Water Isolation Valve Command HXCWIsoVlvCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description

Delay


Numeric 0 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.

2.4.3.2 - Heat Exchanger Chilled Water Isolation Valve is Closed When Condenser Isolation Valve is Open

Summary

Isolation valves on both sides of the heat exchanger should either be both open or closed. 

Equipment Type Equipment Tag Constraints Tuple Constraints
heatExchanger -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Heat Exchanger Chilled Water Isolation Valve Command HXChWIsoVlvCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Heat Exchanger Condenser Water Isolation Valve Command HXCWIsoVlvCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description

Delay


Numeric 0 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.

2.4.4.1 - Heat Exchanger Continuous Operation at High Load

Summary

When the heat exchanger is consistently operated at a load greater than its threshold. 

Equipment Type Equipment Tag Constraints Tuple Constraints
heatExchanger -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Heat Exchanger Chilled Water Isolation Valve Command HXChWIsoVlvCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Heat Exchanger Condenser Water Isolation Valve Command HXCWIsoVlvCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Chilled Water Circulation Pump Status ChWCPSts This point must be a direct child of the equipment that the rule is attached to.  Mandatory Vector
Condenser Water Circulation Pump Status CWCPSts This point must be a direct child of the equipment that the rule is attached to.  Mandatory Vector

Input Constants

Name Data Type Default Value Description

Delay


Numeric 240 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Heat Exchanger Maximum Load Threshold Numeric 95

2.5 Chilled Water Plant

2.5.3.1 - Chilled Water Supply Temperature Greater Than Setpoint

Summary

The chilled water supply temperature is greater than the supply water temperature setpoint, indicating chiller is in a low load situation and is cycling on and off. Chiller does not have modulating control capability, or poor PID tuning.

Equipment Type Equipment Tag Constraints Tuple Constraints
chilled water plant -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Chilled Water Setpoint ChWSp This point must be a direct child of the equipment that the rule is attached to.  Mandatory  Scalar
Chiller Status ChrSts This point must be a direct child of a chiller. Optional Vector
Chilled Water Pump Status ChWCPSts This point must be a direct child of a chiller. Optional Vector
Chilled Water Supply Temperature ChWSTemp This point must be a direct child of the equipment that the rule is attached to.  Mandatory  Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 60 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
THRESHOLD Numeric 2 The temperature threshold.

2.5.4.1 - Chilled Water Supply Temperature Less Than Setpoint

Summary

The chiller water supply temperature is less than the supply water temperature setpoint, indicating poor control programming or poor PID tuning.

Equipment Type Equipment Tag Constraints Tuple Constraints
chilled water plant -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Chilled Water Supply Temperature ChWSTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Chiller Status ChrSts This point must be a direct child of a chiller. Optional Vector
Chilled Water Setpoint ChWSp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Chilled Water Pump Status ChWCPSts This point must be a direct child of a chiller. Optional Vector

Input Constants

Name Data Type Default Value Description
Delay Numeric 60 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
THRESHOLD Numeric 2 The temperature threshold.

2.5.5.1 - Chilled Water Plant Low Temperature Differential (Low Delta T)

Summary

The chilled water plant temperature differential (Delta T) is lower than design.

Equipment Type Equipment Tag Constraints Tuple Constraints
chilled water plant -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Chilled Water Supply Temperature ChWSTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Chiller Status ChrSts This point must be a direct child of a chiller. Mandatory Vector
Chilled Water Return Temperature ChWRTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Chilled Water Pump Status ChWCPSts This point must be a direct child of a chiller. Optional Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 120 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
MIN_DELTA T Numeric 5 The minimum temperature differential. The chilled water return temperature minus the chilled water supply temperature must be less than this constant for a period longer than delay for a fault to exist. 

2.5.6.1 - Chilled Water Supply Temperature Setpoint is Less Than Low Limit

Summary

The chilled water supply temperature setpoint is less than the low limit, wasting energy. The setpoint may be overridden or set lower than design. 

Equipment Type Equipment Tag Constraints Tuple Constraints
chilled water plant -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Chilled Water Setpoint ChWSp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Chiller Status ChrSts This point must be a direct child of a chiller. Mandatory Vector
Chilled Water Pump Status ChWCPSts This point must be a direct child of a chiller. Optional Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 15 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Low Temperature Setpoint Limit Numeric 42

2.5.8.1 - Primary Loop Chilled Water Supply Temperature Sensor Failure

Summary

The primary loop chilled water supply temperature sensor has failed. The temperature sensor point is invariant or is outside the expected range. 

Equipment Type Equipment Tag Constraints Tuple Constraints
chilled water plant -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Chilled Water Supply Temperature ChWSTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Chiller Status ChrSts This point must be a direct child of a chiller. Mandatory Vector
Chilled Water Pump Status ChWCPSts This point must be a direct child of the chiller. Mandatory Vector

Input Constants

Name Data Type Default Value Description
Delay Numeric 120 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
MIN_VALUE Numeric 20 The low threshold.
MAX_VALUE Numeric 100 The high threshold.
VARIANCE Numeric 0.01 The variance threshold.

2.5.8.2 - Chilled Water Return Temperature Sensor Failure

Summary

The chilled water return temperature sensor has failed. The temperature sensor point is invariant or is outside the expected range. 

Equipment Type Equipment Tag Constraints Tuple Constraints
chilled water plant -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Chilled Water Return Temperature ChWRTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Chiller Status ChrSts This point must be a direct child of a chiller. Mandatory Vector
Chilled Water Pump Status ChWCPSts This point must be a direct child of the chiller. Mandatory Vector

Input Constants

Name Data Type Default Value Description
Delay Numeric 120 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
MIN_VALUE Numeric 20 The low threshold.
MAX_VALUE Numeric 70 The high threshold.
VARIANCE Numeric 0.01 The variance threshold

2.5.9.1 - Condenser Water Leaving Temperature Sensor Failure

Summary

The condenser water leaving temperature sensor has failed. The temperature sensor point is invariant or is outside the expected range. 

Equipment Type Equipment Tag Constraints Tuple Constraints
chilled water plant -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Chilled Water Leaving Temperature ChWLTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Chiller Status ChrSts This point must be a direct child of a chiller. Mandatory Vector
Chilled Water Pump Status ChWCPSts This point must be a direct child of the chiller. Mandatory Vector

Input Constants

Name Data Type Default Value Description
Delay Numeric 120 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
MIN_VALUE Numeric 35 The low threshold.
MAX_VALUE Numeric 100 The high threshold.
VARIANCE Numeric 0.01 The variance threshold.

2.5.9.2 - Condenser Water Entering Temperature Sensor Failure

Summary

The condenser water leaving temperature sensor has failed. The temperature sensory point is invariant or is outside the expected range. 

Equipment Type Equipment Tag Constraints Tuple Constraints
chilled water plant -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Chilled Water Entering Temperature ChWETemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Chiller Status ChrSts This point must be a direct child of a chiller. Mandatory Vector
Chilled Water Pump Status ChWCPSts This point must be a direct child of the chiller. Mandatory Vector

Input Constants

Name Data Type Default Value Description
Delay Numeric 120 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
MIN_VALUE Numeric 35 The low threshold.
MAX_VALUE Numeric 100 The high threshold.
VARIANCE Numeric 0.01 The variance threshold.

2.5.10.1 - Outside Air Temperature Sensor Failure

Summary

The outside air temperature sensor has failed. The temperature sensor point is invariant or is outside the expected range. 

Equipment Type Equipment Tag Constraints Tuple Constraints
chilled water plant -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Outside Air Temperature OaTemp This point must be a direct child of the equipment that the rule is attached to.  Mandatory  Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 60 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
MIN_VALUE Numeric -40 The low threshold.
MAX_VALUE Numeric 130 The high threshold.
VARIANCE Numeric 0.01 The variance threshold.

2.5.11.1 - Primary Loop Chilled Water Differential Pressure Setpoint is Excessive

Summary

All chilled water control valves are less than 100% open, not taking full advantage of the reset differential pressure setpoint.

Equipment Type Equipment Tag Constraints Tuple Constraints
chilled water plant -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Cooling Command Primary Heat Exchanger ClgCmdPrimaryHX This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Chilled Water Pressure Differential Setpoint ChWPressDiffSp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Chilled Water Supply Temperature ChWSTemp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Chilled Water Setpoint ChWSp This point must be a direct child of a chiller. Mandatory Scalar
Chilled Water Pressure Differential  ChWPressDiff This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Chilled Water Pressure Differential Setpoint ChWCPStsChiller This point must be a direct child of a chiller. Optional Scalar
Cooling Command ClgCmdAhu This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
AHU Discharge Fan Status DaFanStsAHU This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Fan Status FanSts This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Cooling Command  ClgCmdFcu This point must be a direct child of the equipment that the rule is attached to. Optional Vector
Secondary Heat Exchanger Cooling Command  ClgCmdSecondaryHx This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Secondary Loop Cooling Command ClgCmdSecondaryLoop This point must be a direct child of the rule that it is attached to.  Optional Scalar
Primary Heat Exchanger Chilled Water Pump Status ChWCPStsPrimaryHx This point must be a direct child of the rule that it is attached to.  Optional Vector
Discharge Fan Status DaFanStsUv This point must be a direct child of the rule that it is attached to.  Optional Vector
Cooling Command ClgCmdUv This point must be a direct child of the rule that it is attached to.  Optional Vector
Secondary Heat Exchanger Chilled Water Pump Status ChWCPStsSecondaryHx This point must be a direct child of the rule that it is attached to.  Optional Vector
Secondary Loop Chilled Water Pump Status ChWCPStsSecondaryLoop This point must be a direct child of the rule that it is attached to.  Optional Vector

Input Constants

Name Data Type Default Value Description
Delay Numeric 15 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Heat Exchanger Cooling Command Threshold Numeric 0
Chilled Water Temperature Error Threshold Numeric 2
Maximum Chilled Water Valve Threshold Numeric 90
Differential Pressure Error Threshold Numeric 2

2.5.12.1 - Chilled Water Setpoint Can Be Increased (Reset)

Summary

Where DDC is used to control valves, the chilled water supply temperature set point shall be reset based on valve positions until one valve is nearly wide open or set-point limits of the system equipment or application have been reached.  This would exclude control valves on a secondary loop, which has a control valve to maintain a higher chilled water supply temperature setpoint, but the secondary main control valve should be looked at, when determining the chilled water supply temperature reset value.   Chilled water supply temperature reset is required by ASHRAE Standard 90.1.

Equipment Type Equipment Tag Constraints Tuple Constraints
chiller -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Chiller Enable ChrEnab This point must be a direct child of a chiller. Mandatory Vector
VAV Cooling Command ClgCmd This point must be a direct child of an ahu/fcu. Mandatory Vector
Chilled Water Pump Status ChWCPSts This point must be a direct child of a chiller. Optional Vector
Discharge Air Fan Status DaFanSts This point must be a direct child of an ahu/fcu. Optional Vector
Return Air Humidity RaHumidity This point must be a direct child of an ahu/fcu. Optional Vector
Chilled Water Pump Status ChWCPSts This point must be a direct child of a chiller. Optional Vector
Chilled Water Pump Status ChWCPSts This point must be a direct child of a hx. Optional Vector
Cooling Command ClgCmd This point must be a direct child of a hx. Optional Vector

Input Constants

Name Data Type Default Value Description
Delay Numeric 60 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Valve Threshold Numeric 90 The cooling valve threshold.
Cooling Equipment Percent Numeric 100 Percent of cooling equipment valves below threshold.
Return Air Humidity Numeric 55 Return air humidity high limit. The return air humidity must be less than this constant for a period greater than delay for a fault to exist.
Heat Exchanger Cooling Command Numeric 0 Heat Exchanger command. The ClgCmd must be greater than this constant for a period longer than delay for a fault to exist.

2.5.12.2 - Secondary Loop Chilled Water Supply Temperature Setpoint Could be Raised

Summary

Where DDC is used to control valves, the chilled water supply temperature set point shall be reset based on valve position until one valve is nearly wide open or set-point limits of the system equipment or application have been reached. This would exclude control valves on a secondary loop, which has a control valve to maintain a higher chilled water supply temperature setpoint, but the secondary main control valve should be looked at, when determining the chilled water supply reset value. Chilled water supply temperature reset is required by ASHRAE Standard 90.1-2016, Section 6.5.4.4.

Equipment Type Equipment Tag Constraints Tuple Constraints
chilled water plant -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Chilled Water Supply Temperature ChWSTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Chiller Status ChrSts This point must be a direct child of a chiller. Mandatory Vector
AHU Discharge Fan Status DaFanSts This point must be a direct child of the equipment that the rule is attached to. Optional Vector
Return Air Humidity RaHumidity This point must be a direct child of a chiller. Optional Vector
Chilled Water Setpoint ChWSp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Chilled Water Supply Temperature ChWSTemp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Chiller Chilled Water Pump Status ChWCPStsChiller This point must be a direct child of the equipment that the rule is attached to.  Mandatory Vector
Primary Heat Exchange Chilled Water Pump Status ChWCPStsPrimaryHx This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Primary Heat Exchange Cooling Command ClgCmdPrimaryHx This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
AHU Cooling Command ClgCmdAhu This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Return Air High Humidity Setpoint RaHighHumiditySp This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
FCU Cooling Command ClgCmdFcu This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Fan Status FanSts This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Cooling Command ClgCmdUv This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Discharge Air Fan Status DaFanStsUv This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Tertiary Heat Exchanger Cooling Command ClgCmdTertiaryHx This point must be a direct child of the equipment that the rule is attached to. Optional Vector
Tertiary Heat Exchanger Chilled Water Pump Status ChWCPStsTertiaryHx This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Tertiary Loop Cooling Command ClgCmdTertiaryLoop This point must be a direct child of the equipment that the rule is attached to.  Optional Vector
Tertiary Loop Chilled Water Pump Status ChWCPStsTertiaryLoop This point must be a direct child of the equipment that the rule is attached to.  Optional Vector

Input Constants

Name Data Type Default Value Description
Delay Numeric 60 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Heat Exchanger Cooling Command Threshold Numeric  0
Chilled Water Temperature High Limit Threshold Numeric 50
Chilled Water Temperature Error Threshold Numeric 2
Maximum Chilled Water Valve Threshold Numeric 90
Did this answer your question? Thanks for the feedback There was a problem submitting your feedback. Please try again later.

Still need help? Contact Us Contact Us