5. Building Rules

5.1 Building Rules

5.1.3.1 – Building Outside Air Temperature Sensor Differs From The Local Weather Service Outside Air Temperature

Summary

The building outside air temperature sensor differs from the local weather service outside air temperature.

Equipment Type Equipment Tag Constraints Tuple Constraints
on_prem_weather_station -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Outside Air Temperature OaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Temperature OaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar

Input Constants

Name Data Type Default Value Description
Delay Numeric 360 The delay represents a span of time in minutes during which the sensor must be in a fault state before the rule starts to actually report that it is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time.
Temperature Sensor Threshold Numeric 5 This number (in Fahrenheit) is the temperature sensor threshold.  The difference value of the on-premise temperature and off-premise temperature must exceed the temperature sensor threshold for a period longer than the delay in order for a fault condition to exist.