3.4 Unit Ventilator

3.4.1.1 - Unit Ventilator Simultaneous Heating and Cooling

Summary 

The Unit Ventilator is heating and cooling at the same time, which wastes energy. 

Equipment Type Equipment Tag Constraints Tuple Constraints 
uv -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Cooling Command ClgCmd This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Heating Command HtgCmd This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
DA Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar

Input Constants

Name Data Type Default Value Description 
Delay (minutes) Numeric 0 The delay represents a span of time in minutes during which the vav must be in a fault state before the rule starts to actually report that is is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time. 
Cooling Command Numeric 0 The cooling command threshold.
Heating Command Numeric 0 The heating command threshold. 

3.4.2.1 - Outside Air Flow Damper Position is Greater Than Minimum Setpoint During Heating Mode

Summary

Excess outside air is being brought into the building. The outside air damper is opened greater than the minimum position setpoint during heating mode, except when CO2 levels are higher than CO2 level setpoint when CO2 sensor exists. 

Equipment Type Equipment Tag Constraints Tuple Constraints 
uv -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Outside Air Damper Command (open/closed) OaDmprCmd This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
DA Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Cooling Command ClgCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Heating Command HtgCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory  Scalar
Outside Air Damper Minimum Position Setpoint OaDmprMinPosSp This point must be a direct child of the equipment that the rule is attached to. Mandatory  Scalar
Zone CO2 ZoneCO2 This point must be a direct child of the equipment that the rule is attached to. Optional Scalar
Zone CO2 Setpoint ZoneCO2Sp This point must be a direct child of the equipment that the rule is attached to. Optional Scalar

Input Constants

Name Data Type Default Value Description 
Delay (minutes) Numeric 15 The delay represents a span of time in minutes during which the vav must be in a fault state before the rule starts to actually report that is is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time. 
Cooling Command Numeric 0 The cooling command threshold.
Heating Command Numeric 0 The heating command threshold. 
Outside Air Damper Position Error Numeric 0 The outside air damper position error threshold. 
CO2 Error Numeric 10 The carbon dioxide error threshold.

3.4.3.1 - Outside Air Damper Position is Greater Than Minimum Setpoint During Mechanical Cooling Mode

Summary

Excess outside air is being brought into the building. The Outside Air Damper is greater than the minimum position setpoint during mechanical cooling mode, except when CO2 levels are higher than Co2 level setpoint when Co2 sensor exists or outside air temperatures are lower than the economizer outside air temperature setpoint. 

Equipment Type Equipment Tag Constraints Tuple Constraints 
uv -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
DA Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Outside Air Damper Command (open/closed) OaDmprCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Damper Minimum Position Setpoint OaDmprMinPosSp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Cooling Command ClgCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Heating Command HtgCmd This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Temp OaTemp This point must be a descendant of on_prem_weather_station of this rules equipment ancestor.  Optional Scalar
Outside Air Temp On Prem Weather Station OaTempOnPremWS This point must be a direct child of an off_prem_weather_station attached to this rules equipment ancestor. Optional Scalar
Outside Air Temperature OaTempOffPremWS This point must be a direct child of the equipment that the rule is attached to.  Optional Scalar
Zone CO2 ZoneCO2 This point must be a direct child of the equipment that the rule is attached to.  Optional Scalar
Zone CO2 Setpoint ZoneCO2SP This point must be a direct child of the equipment that the rule is attached to.  Optional Scalar

Input Constants

Name Data Type Default Value Description 
Delay (minutes) Numeric 15 The delay represents a span of time in minutes during which the vav must be in a fault state before the rule starts to actually report that is is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time. 
Cooling Command Numeric 0 The cooling command limit. 
Heating Command Numeric 0 The heating command limit. 
Economizer Outside Air Temperature Numeric 70 The economizer outside air temperature setpoint
Outside Air Damper Position Error Numeric 0 The outside air damper position error threshold. 
CO2 Error Numeric 10 The carbon dioxide error threshold. 

3.4.4.1 - Outside Air Damper is Less Than the Minimum Position Setpoint

Summary

The outside air damper is less than the minimum position setpoint and sufficient ventilation may not be provided.

Equipment Type Equipment Tag Constraints Tuple Constraints 
uv -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Outside Air Damper Command (open/closed) OaDmprCmd This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
DA Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Damper Minimum Position Setpoint OaDmprMinPosSp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Mixed Air Temp MaTemp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar

Input Constants

Name Data Type Default Value Description 
Delay (minutes) Numeric 60 The delay represents a span of time in minutes during which the vav must be in a fault state before the rule starts to actually report that is is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time. 
Low Limit Numeric 40 The mixed air temperature low limit setpoint.

3.4.5.1 - Operating Outside of Schedule

Summary

The Unit Ventilator (UV) is operating outside the defined Occupied Schedule and zone temperature is in-between unoccupied heat and cool setpoints. 

Equipment Type Equipment Tag Constraints Tuple Constraints 
uv -- --

Input Points

Name Point Template Positional Requirements Optionality Multiplicity
Zone Temperature ZoneTemp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
DA Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to.  Optional Scalar
Unoccupied Cooling Setpoint UnoccCoolSp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Unoccupied Heating Setpoint UnoccHeatSp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Occupied Mode Occ This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Da Fan Command (single or common) DaFanCmd This point must be a direct child of the equipment that the rule is attached to.  Optional Scalar

Input Constants

Name Data Type Default Value Description 
Delay (minutes) Numeric 15 The delay represents a span of time in minutes during which the vav must be in a fault state before the rule starts to actually report that is is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time. 

3.4.6.1 - Discharge Air Temperature Sensor Failure

Summary

The temperature sensor point does not change by more than a tolerance of (0.01) or is outside the range (-40 to 250ºF)

Equipment Type Equipment Tag Constraints Tuple Constraints 
uv -- --

Input Points

Name Point Templates Positional Requirements Optionality Multiplicity
Discharge Air Temperature DaTemp This point must be direct child of the equipment that the rule is attached to.  Mandatory Scalar

Input Constants

Name Data Type Default Value Description 
Delay (minutes) Numeric 120 The delay represents a span of time in minutes during which the vav must be in a fault state before the rule starts to actually report that is is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time. 
Maximum Value Numeric 250 The high threshold
Minimum Value Numeric -40 The low threshold
Variance Numeric 0.01 The variance threshold.

3.4.7.1 - Zone Temperature Sensor Failure

Summary


The zone temperature sensor has failed. The temperature sensor is invariant or is outside the expected range. 

Equipment Type Equipment Tag Constraints Tuple Constraints 
uv -- --

Input Points

Name Point Templates Positional Requirements Optionality Multiplicity
Zone Temperature  ZoneTemp This point must be direct child of the equipment that the rule is attached to.  Mandatory Scalar

Input Constants

Name Data Type Default Value Description 
Delay (minutes) Numeric 120 The delay represents a span of time in minutes during which the vav must be in a fault state before the rule starts to actually report that is is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time. 
Maximum Value Numeric 150 The high threshold
Minimum Value Numeric 30 The low threshold
Variance Numeric 0.01 The variance threshold.

3.4.8.1 - Outside Damper Open When Unit is Off

Summary

The Outside Air Damper is open and the supply fan is off, allowing air infiltration. The damper should be shut when the unit is off. 

Equipment Type Equipment Tag Constraints Tuple Constraints 
uv -- --

Input Points

Name Point Templates Positional Requirements Optionality Multiplicity
DA Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Outside Air Damper Position OaDmprPos This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar

Input Constants

Name Data Type Default Value Description 
Delay (minutes) Numeric 120 The delay represents a span of time in minutes during which the vav must be in a fault state before the rule starts to actually report that is is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time. 

3.4.9.1 - Fan Status Off When Commanded On

Summary

The fan status os "Off" but the fan is commanded "On".

Equipment Type Equipment Tag Constraints Tuple Constraints 
uv -- --

Input Points

Name Point Templates Positional Requirements Optionality Multiplicity
DA Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
DA Fan Command (single or common) DaFanCmd This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar

Input Constants

Name Data Type Default Value Description 
Delay (minutes) Numeric 15 The delay represents a span of time in minutes during which the vav must be in a fault state before the rule starts to actually report that is is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time. 

3.4.10.1 - Fan Status On When Commanded Off

Summary

The fan status is "on" but is commanded "off".

Equipment Type Equipment Tag Constraints Tuple Constraints 
uv -- --

Input Points

Name Point Templates Positional Requirements Optionality Multiplicity
DA Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
DA Fan Command (single or common) DaFanCmd This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar

Input Constants

Name Data Type Default Value Description 
Delay (minutes) Numeric 15 The delay represents a span of time in minutes during which the vav must be in a fault state before the rule starts to actually report that is is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time. 

3.4.12.1 - Zone Temperature Setpoint Dead Band is Too Low

Summary

The Zone temperature setpoint dead band is too low. A minimum difference if 5ºF between cooling and heating setpoint is required by ASHRAE Standard 90.1 2016 - Section 6.4.3.1.2. Dead Band.

Equipment Type Equipment Tag Constraints Tuple Constraints 
uv -- EffCoolSp & EffHeatSp || OccCoolSp & OccHeatSp

Input Points

Name Point Templates Positional Requirements Optionality Multiplicity
Occupied Cooling Setpoint OccCoolSp This point must be a direct child of the equipment that the rule is attached to. Optional Scalar
Occupied Heating Setpoint OccHeatSp This point must be a direct child of the equipment that the rule is attached to.  Optional Scalar
Effective Cooling Setpoint EffCoolSp This point must be a direct child of the equipment that the rule is attached to.  Optional Scalar
Effective Heating Setpoint EffHeatSp This point must be a direct child of the equipment that the rule is attached to.  Optional Scalar

Input Constants

Name Data Type Default Value Description 
Delay (minutes) Numeric 30 The delay represents a span of time in minutes during which the vav must be in a fault state before the rule starts to actually report that is is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time. 
Deadband Numeric 5 The minimum temperature dead band allowed. 

3.4.13.1 - Unexpected Temperature Decrease Across Cooling Coil

Summary

There is a decrease in temperature across the cooling coil with valve closed, indicating the cooling valve may be leaking. This will lead to increased operating costs and comfort complaints. 

Equipment Type Equipment Tag Constraints Tuple Constraints 
uv -- --

Input Points

Name Point Templates Positional Requirements Optionality Multiplicity
DA Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Discharge Air Temperature DaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Mixed Air Temp MaTemp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Cooling Command ClgCmd This point must be a direct child fo the equipment that the rule is attached to.  Mandatory Scalar

Input Constants

Name Data Type Default Value Description 
Delay (minutes) Numeric 30 The delay represents a span of time in minutes during which the vav must be in a fault state before the rule starts to actually report that is is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time. 
Valve Threshold Numeric 1 The valve command threshold.
Delta T Numeric 3 The max temperature decrease allowed across coil.

3.4.14.1- Unexpected Temperature Increase Across Heating Coil

Summary

There is an increase in temperature across the heating coil with valve closed, indicating the heating valve may be leaking or sensor(s) is out of calibration. This will lead tp increased operating cost and comfort complaints. 

Equipment Type Equipment Tag Constraints Tuple Constraints 
uv -- --

Input Points

Name Point Templates Positional Requirements Optionality Multiplicity
DA Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Discharge Air Temperature DaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Mixed Air Temp MaTemp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Heating Command HtgCmd This point must be a direct child fo the equipment that the rule is attached to.  Mandatory Scalar

Input Constants

Name Data Type Default Value Description 
Delay (minutes) Numeric 30 The delay represents a span of time in minutes during which the vav must be in a fault state before the rule starts to actually report that is is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time. 
Valve Threshold Numeric 1 The valve command threshold.
Delta T Numeric 3 The max temperature decrease allowed across coil.

3.4.15.1 - Freezestat Has Tripped

Summary

The Freezestat has sensed a potential freezing condition and has shutdown the unit to prevent damage to the unit. 

Equipment Type Equipment Tag Constraints Tuple Constraints 
uv -- --

Input Points

Name Point Templates Positional Requirements Optionality Multiplicity
Freeze Status FreezeStat This point must be a direct child of the equipment that the rule is attached to.  Mandatory  Scalar

Input Constants

Name Data Type Default Value Description 
Delay (minutes) Numeric 0 The delay represents a span of time in minutes during which the vav must be in a fault state before the rule starts to actually report that is is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time. 

3.4.17.1 - Leaving Preheat Coil Temperature is Falling Below Low Limit Temperature Setpoint

Summary

The temperature leaving the preheat coil is below low limit temperature setpoint, which could lead to freezestat trips or freezing coil. 

Equipment Type Equipment Tag Constraints Tuple Constraints 
uv -- --

Input Points

Name Point Templates Positional Requirements Optionality Multiplicity
Mixed Air Temperature Low Limit Setpoint MaTempLoLmtSp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
PreHeat Coil Air Leaving Temp PreHCALTemp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar

Input Constants

Name Data Type Default Value Description 
Delay (minutes) Numeric 0 The delay represents a span of time in minutes during which the vav must be in a fault state before the rule starts to actually report that is is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time. 
Threshold Numeric  0.5 The preaheat coil leaving air temperature error threshold. 

3.4.18.1 - Mixed Air Dampers Unable to Meet Discharge Air Temperature Setpoint When Outside Air Temperature is Low Enough

Summary

When mixed air dampers are 100% and outside air temperature is low enough to meet discharge air temperature setpoint, but cannot meet setpoint. 

Equipment Type Equipment Tag Constraints Tuple Constraints 
uv -- OaTemp || OaTempOnPremWS || OaTempOffPremWS

Input Points

Name Point Templates Positional Requirements Optionality Multiplicity
DA Temp Setpoint DaTempSp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Da Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Discharge Air Temperature DaTemp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Outside Air Temperature OaTemp This point must be a direct child of the equipment that the rule is attached to.  Optional Scalar
Outside Air Temperature Off Prem Weather Station OaTempOffPremWS This point must be a direct child of the this rules equipment ancestors child off prem weather station. Optional Scalar
Outside Air Temperature On Prem Weatherstation OaTempOnPremWS This point must be a direct child of this rules equipment ancestors child on prem weather station.  Optional Scalar

Input Constants

Name Data Type Default Value Description 
Delay (minutes) Numeric 15 The delay represents a span of time in minutes during which the vav must be in a fault state before the rule starts to actually report that is is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time. 
Threshold Numeric  5 The preaheat coil leaving air temperature error threshold. 

3.4.19.1 - Outside Air Temperature Too High For Free Cooling Only

Summary

Outside air temperature too high for free cooling without additional mechanical cooling. 

Equipment Type Equipment Tag Constraints Tuple Constraints 
uv -- OaTemp || OaTempOnPremWS || OaTempOffPremWS & EffCoolSp || OccCoolSp || ZoneTempSp

Input Points

Name Point Templates Positional Requirements Optionality Multiplicity
Da Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Heating Command HtgCmd This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Cooling Command ClgCmd This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Outside Air Damper Position OaDmprPos This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Outside Air Temperature OaTemp This point must be a direct child of the this rules equipment ancestors child off prem weather station. Mandatory Scalar
Effective Cooling Setpoint EffCoolSp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Zone Temperature ZoneTemp This point must be a direct child of the equipment that the rule is attached to.  Optional Scalar
Outside Air Temperature On Prem Weatherstation OaTempOnPremWS This point must be a descendant of this rules equipment ancestor Optional Scalar
Occupied Cooling Setpoint OccCoolSp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Zone Temperature Setpoint (effective) ZoneTempSp This point must be a direct child of the equipment that the rule is attached to.  Optional Scalar
Outside Air Temperature Off Prem Weather Station OaTempOffPremWS This point must be a ddescendant of this rules equipment ancestor. Optional Scalar

Input Constants

Name Data Type Default Value Description 
Delay (minutes) Numeric 15 The delay represents a span of time in minutes during which the vav must be in a fault state before the rule starts to actually report that is is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time. 
Heating Command Numeric 0 The heating command threshold.
Cooling Command Numeric 0 The cooling command threshold. 
Outside Air Temperature Limit Numeric 70 The outside air temperature limit threshold. 
Outside Air Damper Position Numeric 100 The outside air damper position threshold. 

3.4.20.1 - Outside and Mixed Temperature Should be Approximately Equal During Mechanical and Free Cooling Mode

Summary

Outside and mixed air temperature should be approximately equal during mechanical and free cooling mode. 

Equipment Type Equipment Tag Constraints Tuple Constraints 
uv -- OaTemp || OaTempOnPremWS || OaTempOffPremWS 

Input Points

Name Point Templates Positional Requirements Optionality Multiplicity
Mixed Air Temp MaTemp This point must be a direct child of the equipment that the rule is attached to. Mandatory Scalar
Da Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Heating Command HtgCmd This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Cooling Command ClgCmd This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Outside Air Damper Position OaDmprPos This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Outside Air Temperature On Prem Weather Station OaTempOnPremWS This point must be a descendant of this rule's ancestor.  Optional Scalar
Outside Air Temperature OaTemp This point must be a direct child of the equipment that the rule is attached to.  Optional Scalar
Outside Air Temperature Off Prem Weather Station OaTempOffPremWS This point must be a child of this rules ancestor. Optional Scalar

Input Constants

Name Data Type Default Value Description 
Delay (minutes) Numeric 15 The delay represents a span of time in minutes during which the vav must be in a fault state before the rule starts to actually report that is is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time. 
Mixed Air Temperature Error Numeric 5 The mixed air temperature error threshold. 
Outside Air Temperature Error Numeric 2 The outside air temperature error threshold. 
Heating Command Numeric 0 The heating command threshold.
Cooling Command Numeric 0 The cooling command threshold. 
Outside Air Damper Position Numeric 100 The outside air damper position threshold. 

3.4.21.1 - Outside Air Temperature Too Low for 100% Outside Air Cooling During Mechanical and Free Cooling Mode

Summary

Outside air temperature is too low for 100% outside air cooling during mechanical and free cooling mode. 

Equipment Type Equipment Tag Constraints Tuple Constraints 
uv -- OaTemp || OaTempOnPremWS || OaTempOffPremWS 

Input Points

Name Point Templates Positional Requirements Optionality Multiplicity
Mixed Air Temperature Low Limit Setpoint MaTempLoLmtSp Mandatory Scalar
Da Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Heating Command HtgCmd This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Cooling Command ClgCmd This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Outside Air Damper Position OaDmprPos This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Outside Air Temperature On Prem Weather Station OaTempOnPremWS This point must be a descendant of this rule's ancestor.  Optional Scalar
Outside Air Temperature OaTemp This point must be a direct child of the equipment that the rule is attached to.  Optional Scalar
Outside Air Temperature Off Prem Weather Station OaTempOffPremWS This point must be a child of this rules ancestor. Optional Scalar

Input Constants

Name Data Type Default Value Description 
Delay (minutes) Numeric 15 The delay represents a span of time in minutes during which the vav must be in a fault state before the rule starts to actually report that is is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time. 
Discharge Air Temperature Error Numeric 5 The discharge air temperature error threshold. 
Outside Air Temperature Error Numeric 2 The outside air temperature error threshold. 
Heating Command Numeric 0 The heating command threshold.
Cooling Command Numeric 0 The cooling command threshold. 
Outside Air Damper Position Numeric 100 The outside air damper position threshold. 
Discharge Air Fan Temperature Numeric 2 The discharge air fan temperature rise threshold. 

3.4.22.1 - Discharge Air Temperature Too High During Mechanical and/or Free Cooling

Summary

Discharge air temperature too high during mechanical and/or free cooling; should be less than mixed air temperature. 

Equipment Type Equipment Tag Constraints Tuple Constraints 
uv -- --

Input Points

Name Point Templates Positional Requirements Optionality Multiplicity
Da Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Discharge Air Temperature DaTemp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Mixed Air Temp MaTemp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Heating Command HtgCmd This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Cooling Command ClgCmd This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Outside Air Damper Position OaDmprPos This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Outside Air Damper Minimum Position Setpoint OaDmprMinPosSp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar

Input Constants

Name Data Type Default Value Description 
Delay (minutes) Numeric 15 The delay represents a span of time in minutes during which the vav must be in a fault state before the rule starts to actually report that is is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time. 
Discharge Air Fan Temperature Numeric 2 The discharge air fan temperature threshold. 
Mixed Air Temperature Error Numeric 5 The mixed air temperature error threshold. 
Heating Command Numeric 0 The heating command threshold.
Outside Air Damper Position Numeric 100 The outside air damper position threshold. 
Discharge Air Temperature Error Numeric 2 The discharge air temperature error threshold. 
Cooling Command Numeric 0 The cooling command threshold. 

3.4.23.1 - Discharge Air Temperature Too High in Full Cooling

Summary

Discharge air temperature too high in full cooling during full mechanical cooling.

Equipment Type Equipment Tag Constraints Tuple Constraints 
uv -- --

Input Points

Name Point Templates Positional Requirements Optionality Multiplicity
Da Fan Status (single or common) DaFanSts This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Discharge Air Temperature DaTemp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Mixed Air Temp MaTemp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Heating Command HtgCmd This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Cooling Command ClgCmd This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Outside Air Damper Position OaDmprPos This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Outside Air Damper Minimum Position Setpoint OaDmprMinPosSp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Effective Cooling Setpoint EffCoolSp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Occupied Cooling Setpoint OccCoolSp This point must be a direct child of the equipment that the rule is attached to.  Mandatory Scalar
Zone Temperature Setpoint (effective) ZoneTempSp This point must be a direct child of the equipment tat the rule is attached to.  Mandatory Scalar

Input Constants

Name Data Type Default Value Description 
Delay (minutes) Numeric 15 The delay represents a span of time in minutes during which the vav must be in a fault state before the rule starts to actually report that is is in a fault state. The intent of the delay is to reduce the level of alert noise by ensuring that the system does not alert until the fault condition has been in effect for some minimal interval of time. 
Discharge Air Temperature Numeric 2 The discharge air temperature error threshold.
Maximum Cooling Command Numeric 99 The maximum cooling command threshold. 
Heating Command Numeric 0 The heating command threshold.